3 setup site id, 4 connect battery, Table 25 battery alarms – Emerson Autochangeover Controllers AC8 User Manual

Page 67: Setup site id, Connect battery, Table 25, Battery alarms

Advertising
background image

System and Control Options

59

7.9.3 Setup Site ID

You may enter a Site ID to identify the AC8’s location, using a name

that may consist of up to 40 characters (see Table 14 for valid charac-

ters). The Site ID will appear with each alarm.
To enter or change the Site ID:

• From the Setup System Info Menu, use the arrows

↑↓

to

choose

Setup Site ID, then press Enter

.

• To enter a Site ID:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• If the Site ID is less than 40 characters, you may enter an

underscore (_) character to indicate the end of the name.

• When finished, press Enter

again.

7.9.4 Connect Battery

By default, the AC8 checks the battery and sounds an alarm when the power fails, the battery runs

low or the battery needs to be checked. The battery’s main purpose is to provide enough power to the

modem to notify pagers of a power loss.

Using the following procedure to disconnect the battery will disable battery alarm features only. The

battery itself will continue to provide backup. If battery backup is not desired, the battery must be

unplugged from the circuit board. This can be done by removing the battery leads from the jumpers

(see 2.4.2 - Connecting the Battery Pack).
The default is to connect the battery. However, there may be times that you want to disconnect the

battery so that it does not provide backup.
Table 25 shows battery problems that will affect operation.

To connect or disconnect the battery:

• From the Setup System Info Menu, use the arrows

↑↓

to

choose

Connect Battery, then press Enter

.

• Use the arrows

↑↓

to choose Y (Yes - the battery is connected) or

N (No - the battery is not connected), then press Enter

.

NOTE
The battery will continue to power and provide full operation of the AC8 with the exception of

powering the analog inputs (sensors). The battery will provide backup for a minimum of 10

minutes.

Table 25

Battery alarms

Result of Battery

Action

Message Generated

Battery falls below a minimum charge.

Battery will not provide battery backup.

LOW BATTERY

Battery is connected to the circuit board but

not recognized by the circuit board.

Battery will not provide battery backup.

CHECK BATTERY

Battery is unplugged from the circuit board.

Battery will not provide battery backup

BATTERY UNPLUGGED

Utility power (24VAC) to the circuit board is

too low to power the board.

AC8 board will not be able to function

properly.

LOSS OF POWER

Setup System Info Menu

SETUP SYSTEM INFO

CHANGE PASSWORD
CHANGE DATE & TIME

↑↓

=NEXT

=SELECT

> SETUP SITE ID

CONNECT BATTERY
SETUP SERV PH NUM
FACTORY DEFAULTS

Setup Site ID

SETUP SITE ID

AAAAAAAAAAAAAAAAAAAA
AAAAAAAAAAAAAAAAAAAA

↑↓

=SELECT

=NEXT/END

Setup System Info Menu

SETUP SYSTEM INFO

CHANGE PASSWORD
CHANGE DATE & TIME

↑↓

=NEXT

=SELECT

SETUP SITE ID

> CONNECT BATTERY

SETUP SERV PH NUM
FACTORY DEFAULTS

Connect Battery

IS THE BATTERY
CONNECTED? Y

↑↓

=Y/N

=END

Advertising