7.12 Override Output

The Override Output feature allows you to manually change the state of any digital output to ON or

OFF, overriding automatic control by the AC8 (the default setting for all outputs). This menu also

allows you to release the manual override, returning any output to automatic control.
There are two ways to override automatic control of outputs:

• Use the Override Output menu, as described in this section, to turn any output ON or OFF.
• Use the hardware switch on the AC8 circuit board to force all eight outputs ON at the same time

(see Item I - Manual Override Switch (outputs) in 1.7 - Controller Board Overview).

After an output is forced manually ON or OFF through the Override Output menu, it remains in that

state until returned to automatic control through this menu.
Table 32 summarizes the four types of control, including the abbreviated message that appears on

the LCD and in log reports.

To force an output point ON or OFF or return it to automatic control:

Log In and Choose Override Output

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Override Output, then press Enter

.

Select an Output
The Select Output menu, shown at right, displays the current status of

all eight outputs.

• Use the arrows

↑↓

to

choose the output you want—for example,

Device_1—and press Enter

.

Turn Output ON or OFF / Return to Automatic

• From the Override Output menu, use the arrows

↑↓

to

choose one

of these options:

AUTO - return to automatic control
FORCE ON - manually turn this output ON (operating)
FORCE OFF - manually turn this output OFF

• Press Enter

.

Table 32

Automatic / manual control - output points

Message

Description

AUTO

Automatic

Controlled by AC8

(default for all outputs)

FORCE ON

Manually ON

This output has been forced ON

(operating) or OFF via the Override

Output menu

FORCE OFF

Manually OFF

HW FORCE ON

Manually ON

(all outputs)

All outputs have been forced ON

(operating) via the hardware switch on

the circuit board (see Item I - Manual

Override Switch (outputs) in 1.7 -

Controller Board Overview)

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

Login

LOGIN

AAAA

↑↓

=SELECT

=NEXT/END

System & Control Menu

SETUP SYSTEM

> OVERRIDE OUTPUT

CLEAR ALARMS & LOGS

↑↓

=NEXT

=SELECT

Select Output

OVERRIDE OUTPUT

> DEVICE_1

AUTO

DEVICE_2

AUTO

↑↓

=NEXT

=SELECT

DEVICE_3 AUTO
DEVICE_4 FORCE ON

Override Output

SELECT DEVICE_1

FORCE ON

↑↓

=SELECT

=END