7.10 Setup Operation

The AC8’s operation features allow you to set up a rotation sequence to

alternate which devices are operating and which are placed on

Standby, as well as test devices while in Standby mode and specify

what to do when a Standby device goes into alarm as it is powered up.

You may specify delay times after an output changes state, directing

the AC8 to wait before acknowledging inputs (hold delay time) or turn-

ing an output on or off (restart delay time). With staging, you may con-

figure the AC8 to turn a standby device on or off when an analog sensor

detects a condition above or below specified levels.
To change any operation feature:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select Setup Operation

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Operation and press Enter

.

Select a Zone to Configure

• From the Select Zone Menu, use the arrows

↑↓

to choose the zone

you want—for example, Zone_1—and press Enter

.

• Use the steps following Table 28 to access any of the Setup Opera-

tion options.

Table 28 shows the default settings for operation options: automatic sequencing, standby testing,

failed standby, hold delay, restart and staging.

Figure 12 provides an overview of the Setup Operation screens available via the LCD interface.

Figure 12 Menu overview - Setup Operation menu

Table 28

Default settings - operation features

Feature

Default

Other Options

AUTO SEQUENCING

OFF (Deactivated)

ON (Activated), 12h (Activated for 12-hour intervals)

STANDBY TESTING

OFF (Deactivated)

ON (Activated)

FAILED STANDBY

N (Deactivated)

Y (Activated)

HOLD DELAY

10:00 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

RESTART

00:06 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

STAGING

OFF (Deactivated)

ON (Activated)

Setup System Menu

SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR

↑↓

=NEXT

=SELECT

SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO

> SETUP OPERATION

SETUP I/O MATRIX

Select Zone Menu

SELECT ZONE FOR
THE OPERATION

>

ZONE 1

↑↓

=NEXT

=EDIT

Setup Operation Menu

> AUTO SEQUENCING OFF

STANDBY TESTING OFF
FAILED STANDBY

N

↑↓

=NEXT

=SELECT

HOLD DELAY : 10:00
RESTART

: 00:06

STAGING

: OFF

Setup Operation

AUTO SEQUENCING OFF
STANDBY TESTING OFF
FAILED STANDBY

N

HOLD DELAY : 10:00
RESTART

: 00:06

STAGING

: OFF

Auto Sequencing

Standby Testing

Failed Standby

AUTO SEQUENCING ON
EVERY 03 DAYS
AT 00:00

See

Section

7.10.1

> STANDBY TESTING ON

EVERY 03 DAYS
AT 00:00 FOR 10 MIN

See

Section

7.10.2

FAILED STANDBY

N

See

Section

7.10.3

Hold Delay

Restart

Staging

HOLD DELAY

10 MIN : 00 SEC

See

Section

7.10.4

RESTART DELAY

00 MIN : 06 SEC

See

Section

7.10.5

STAGING: ON
TARGET: +0070.0
SENSITIVITY: +005.0

See

Section

7.10.6

Setup Operation options