3.2.4 Connecting Control Relay Outputs

To connect a control relay output:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to

permit wire entry into the AC8 enclosure.

3. Bring the wire(s) into the AC8 enclosure

through a conduit knockout or access slot.

4. Loosen the appropriate screw and slip the

stripped end of the wire into the terminal

block.

5. Tighten the screw until it holds the wire

snugly.

3.2.5 Connecting the Emergency Power Operation (EPOP) Input

The emergency power operation, or EPOP, input connector block (TB1) is at the bottom right corner of

the AC8 printed circuit board, just below the digital inputs.
To determine the proper wire size, see Table 4 - Wiring specifications.
To connect to the EPOP input:
1. Turn OFF electrical power to the AC8.
2. If necessary, remove a conduit knockout to permit

wire entry into the AC8 enclosure.

3. Bring the wire into the AC8 enclosure through a

conduit knockout or access slot.

4. Loosen each screw and slip the stripped end of the

wire into the terminal block.

5. Tighten each screw until it holds the wire snugly.

3.2.6 Setting the EPOP Jumper

The EPOP contact input has an associated jumper to

enable or disable emergency power operation (EPOP).
The AC8 comes from the factory with the EPOP jumper in

the Disabled position (DIS); it may be changed to Enabled

(EN).
To change the EPOP jumper setting:
1. Find the black EPOP jumper on the circuit board, as

shown at right. The jumper is at the bottom right

corner of the board just below the EPOP contact input

(see 1.7 - Controller Board Overview).

2. Decide whether your configuration requires the jumper to be enabled or disabled.
3. Set the jumper as needed:

• To enable EPOP, place the black jumper on the middle and right pins. The right side of the

jumper is labeled EN for Enabled.

• To disable EPOP, place the black jumper on the middle and left pins. The left side of the

jumper is labeled DIS for Disabled.

!

CAUTION

To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2

circuits.

NOTE
When the EPOP jumper is set to Enabled, a Normally Closed contact must be attached or an

alarm will be generated and the outputs will default to the EPOP operation setting.

RELAY

OUTPUTS

TB4:

(BOTTOM)

2

(BOTTOM)

(TOP)

8

NC

C

NO

NC

C

NO

ON

PFM3

OFF

ON

PFM8

OFF

NUMBERING KEYS -

Relay 1 at left (green);

Relay 2 at right (black)

RELAY OUTPUT

TERMINAL BLOCKS

TB2:

CONTACT

INPUTS

ASS

EPOP

EPOP INPUT

EPOP

P19

TB1

DIS EN

REV

ONON

PFM5

OFF

1

5

(BOTTOM)

(TOP)

4

3

2

1

8

7

6

5

TB1: EPOP

CONTACT

INPUT

TB1, TB2 INPUTS:

DRY CONTACTS ONLY.

ON

PF

EPOP

jumper

EPOP

input

Advertising