7 setup system - setup outputs, Table 19 default settings - digital outputs, Setup system - setup outputs – Emerson Autochangeover Controllers AC8 User Manual

Page 55: Define output as normally open or normally closed, Table 19, Default settings - digital outputs

Advertising
background image

System and Control Options

47

7.7

Setup System - Setup Outputs

The AC8 has eight outputs that may be configured individually. These outputs correspond to the

eight numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.
The output name is the same as the input name, as described in 7.3.1 -

Change Label (Name of Input).
To configure an output:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select an Output to Configure

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Outputs and press Enter

.

• From the Select Output Menu, choose an output—for example,

Device_1—and press Enter

.

Table 19 shows digital output features and their default settings: you

may define an output as Normally Open or Normally Closed, set the

device’s mode—operating, standby or not used—and specify whether to

disable the device during emergency power operation.
Use the steps following Table 19 to change the default settings for any

digital output.

7.7.1 Define Output as Normally Open or Normally Closed

Each output may be set up as Normally Open (NO) or Normally Closed

(NC). The default setting for all output points is NO (Normally Open).

• From the Setup Outputs Menu, shown at right, use the arrows

↑↓

to

choose Norm Open/Close and press Enter

.

• To change the normal state for this output, use the arrows

↑↓

to

choose the state:

NO (Normally Open)
NC (Normally Closed)

• Press Enter

.

Table 19

Default settings - digital outputs

Feature

Default

Other Options

NORM OPEN/CLOSE

NO (Normally Open)

NC (Normally Closed)

MODE*

Outputs 1-2:

Outputs 3-4:

Outputs 5-8:

OP (Operating)

ST (Standby)

NU (Not Used)

OP (Operating)

ST (Standby)

NU (Not Used)

IN ALARM

E (Enable)

D (Disable)

EMERG OP

E (Enable)

D (Disable)

* Outputs defined as Not Used should be kept in a separate zone that does not include

any outputs defined as Operating or Standby. The Auto Sequencing feature will not
function properly in a zone with outputs defined as Not Used. See 7.10.1 - Turn
Automatic Sequencing On or Off
for more information.

Setup System Menu

SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR

↑↓

=NEXT

=SELECT

SETUP ZONES

> SETUP OUTPUTS

SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX

Select Output Menu

SELECT OUTPUT

> DEVICE_1

NO-OP-E-E

DEVICE_2

NO-ST-E-E

↑↓

=NEXT

=SELECT

DEVICE_3

NO-ST-E-E

DEVICE_4

NO-ST-E-E

DEVICE_5

NO-NU-E-E

DEVICE_6

NO-NU-E-E

DEVICE_7

NO-NU-E-E

DEVICE_8

NO-NU-E-E

Setup Outputs Menu

SETUP DEVICE_1

> NORM OPEN/CLOSE: NO

MODE: OPERATING

↑↓

=NEXT

=SELECT

IN ALARM: ENABLE
EMERG OP: ENABLE

Change State

SET TO NORMAL OPEN
OR NORMAL CLOSE? NO

↑↓

=NO/NC

=END