36

7.2

Setup System - Overview

The Setup System screen displays seven options that allow you to configure input and output

devices and their relationships, the common alarm, the modem, pagers to be dialed when alarms

occur, and a variety of system details, such as login password and system date and time:

• Setup Inputs
• Setup Common Alarm
• Setup Sensor
• Setup Zones
• Setup Outputs
• Setup Modem & Pagers
• Setup System Info
• Setup Operation
• Setup I/O Matrix

7.3

Setup System - Setup Inputs

The AC8 has eight digital input points that may be configured

individually. These inputs may have a wide variety of Liebert or other

manufacturers’ equipment connected for monitoring.
To configure a digital input:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select a Digital Input to Configure

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Inputs and

press Enter

.

• From the Select Input Menu, choose the input you want—for example, Device_1—and press

Enter

.

Table 15 shows the digital input features you may change, along with the default settings: you may

change the name of the input, define it as Normally Open or Normally Closed, and specify it as alarm-

able or as an event.

• Alarmable inputs may be defined as either Unlatched or Latched.
• Event status allows you to monitor a digital input’s state—and use a change in state to initiate an

action through an output, if desired—without triggering an alarm. Events are always Unlatched.

• You may also specify a time delay before the AC8 responds to an alarm or event.

Use the steps following Table 15 to change the default settings for any digital input.
Table 15

Default settings - digital inputs

Feature

Default

Other Options

LABEL

DEVICE_1

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally Open)

NC (Normally Closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

L (Latched) / Y (Yes)*

NL (Unlatched) / N (No)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

Settings - Select Input
Menu (see Section 7.3)

When configuring an input
(see Section 7.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)

Setup System Menu

> SETUP INPUTS

SETUP COMMON ALARM
SETUP SENSOR

↑↓

=NEXT

=SELECT

SETUP ZONES
SETUP OUTPUTS
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX

Select Input Menu

SELECT INPUT

> DEVICE_1 NO-AL-L

DEVICE_2 NO-AL-L

↑↓

=NEXT

=SELECT

DEVICE_3 NO-AL-L
DEVICE_4 NO-AL-L
DEVICE_5 NO-AL-L
DEVICE_6 NO-AL-L
DEVICE_7 NO-AL-L
DEVICE_8 NO-AL-L