7.5.9 Change Low Setpoint

When the sensor detects a condition below the Low Setpoint value, an

alarm or event will occur, depending on the sensor configuration.
The Low Setpoint value must not be set below the sensor’s 4 mA value

plus the offset value. For example, if the 4 mA value is 50°F and the

Offset value is 5°F, the Low Setpoint must be 55°F or higher.
The default Low Setpoint for each sensor is +0050.0. Values that can

be entered range from:

• the 4 mA value + the Offset value (in the example, 50+5=55)

to

• the 20 mA value + the Offset value (in the example, 90+5=95)

To view or change these values, see 7.5.4 - Change 4 mA Value,

7.5.5 - Change 20 mA Value and 7.5.6 - Change Offset Value.
To enter a new value:

• From the Setup Sensor Menu, choose Low Setpt for the selected

sensor and press Enter

.

• To change the Low Setpoint:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

7.5.10 Change High Setpoint

When the sensor detects a condition above the High Setpoint value, an

alarm or event will occur, depending on the sensor configuration.
The High Setpoint value must not be set above the sensor’s 20 mA value

plus the offset value. For example, if the 20 mA value is 90°F and the

Offset value is 5°F, the High Setpoint must be 95°F or lower.
The default High Setpoint for each sensor is +0090.0. Values that can

be entered range from:

• the 4 mA value + the Offset value (in the example, 50+5=55)

to

• the 20 mA value + the Offset value (in the example, 90+5=95)

To view or change these values, see 7.5.4 - Change 4 mA Value,

7.5.5 - Change 20 mA Value and 7.5.6 - Change Offset Value.
To enter a new value:

• From the Setup Sensor Menu, choose High Setpt for the selected

sensor and press Enter

.

• To change the High Setpoint:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED: Y
LABEL: ROOM_TMP

↑↓

=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N

> LOW SETPT: +0050.0

HIGH SETPT: +0090.0
SENSOR DELAY: 00:01

Change Low Setpoint

CHANGE LOW SETPOINT

LOW SETPT: +0060.0

↑↓

=SELECT

=NEXT/END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED: Y
LABEL: ROOM_TMP

↑↓

=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET:

+005.0

ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0060.0

> HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change High Setpoint

CHANGE HIGH SETPOINT

HIGH SETPT: +0085.0

↑↓

=SELECT

=NEXT/END