Table 23, Number and pin – Emerson Autochangeover Controllers AC8 User Manual

Page 61

Advertising
background image

System and Control Options

53

7.8.3 Pager Setup - Pager Number and PIN

The AC8 may be configured to dial numeric or alphanumeric pagers when an alarm is detected. You

may enter up to four pager numbers—all configured pagers will be dialed each time an alarm occurs.

For each configured pager, you must enter the pager number to be dialed and the pager’s Personal

Identification Number (PIN).
See 8.1 - AC8 Specifications for supported pager settings.
The AC8 can send numeric or alphanumeric messages to supported pagers, as shown in the following

example:

When an alarm is detected, the first pager number is dialed—up to three times, if needed. After a suc-

cessful page or three dialing attempts, the next pager number is dialed, again with three attempts as

needed, and so on for all configured pagers.

To configure a pager:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select a Pager to Configure

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Modem&Pagers and press Enter

.

• Use the arrows

↑↓

to

choose Setup Pagers from the Pagers &

Modem Menu, and press Enter

.

• From the Select Pager Menu, choose the pager number you

want—for example, Pager Number 1—and press Enter

.

Table 23

Pager dialing results

Result of Page

Action

Message Generated

Successful

AC8 dials next configured pager.

Unsuccessful due to:

Busy signal / no answer /

no dial tone

AC8 generates message after all three redial attempts

have failed, dials next configured pager.

Unsuccessful Page

(Event Log)

General modem

communication problem

AC8 resets modem, generates message, redials pager

up to three more times.

Modem Reset

(Event Log)

No communication with

modem

(internal hardware problem)

AC8 generates messages, makes no further dialing

attempts.

Modem Internal Fault

(Active Alarm Report,

Alarm History Log)

LIEBERT TEST

DEVICE_1 ALARM

CONTACT CLOSED

2:07 PM 06/09/04

Alphanumeric pager

message example

Pager company time stamp

Setup System Menu

SETUP INPUTS
SETUP COMMON ALARM
SETUP SENSOR

↑↓

=NEXT

=SELECT

SETUP ZONES
SETUP OUTPUTS

> SETUP MODEM&PAGERS

SETUP SYSTEM INFO
SETUP OPERATION
SETUP I/O MATRIX

Pagers & Modem Menu

> SETUP PAGERS

SETUP MODEM

↑↓

=NEXT

=SELECT

Select Pager Menu

SELECT PAGER

> PAGER NUMBER 1

PAGER NUMBER 2

↑↓

=NEXT

=SELECT

PAGER NUMBER 3
PAGER NUMBER 4

Advertising