View Status Options

26

5.5

View Input Status

The Input Status option allows you to view the current status of all

inputs: the four analog sensor inputs and the eight digital inputs.
To view the Input Status:

• From the Main Menu, use the arrows

↑↓

to

choose View Status,

then press Enter

↵.

• From the View Status Menu, use the arrows

↑↓

to

choose View

Input Status, then press Enter

.

5.5.1 Input Status

The Input Status screen displays the status of each analog sensor and

digital input.

Analog Sensor Inputs
The following details are displayed for analog sensor inputs:

• the name of the analog sensor input (for example,

SENSOR_1

)

• the current reading (

+80.00 DEG

)—values are updated constantly

while being viewed

There are three possible states for an analog input, as shown in

Table 11.

Digital Inputs
The following details appear for digital inputs:

• the name of the digital input (for example,

DEVICE_1

)

• the current status (

NORMAL

)—values are updated constantly while being viewed

There are three possible states for a digital input, as shown in Table 12.

Viewing Additional Input Data

All input data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:

• To view all inputs, use the arrows

↑↓

.

• To return to the previous screen, press the ESC key.

Table 11

Analog input states

State

Description

Functional

Reading—-for example,

+80.00 DEG or +79.50 RH

Problem with

connection

Dashes (

------

)

Not configured

Blank

NOTE
If the status displays dashes (

------

), the AC8 was unable to take a reading. There may be a

connection problem.
If the status is blank, the sensor is not configured as being connected.

Table 12

Digital input states

State

Description

NORMAL

In normal state

ALARM

In alarm status (for an input configured as alarmable)

EVENT

An event has occurred (for an input configured as an event)

Main Menu

> VIEW STATUS

SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

View Status Menu

VIEW ACTIVE ALARMS
VIEW ALARM LOG
VIEW EVENT LOG
VIEW TREND LOG

> VIEW INPUT STATUS

VIEW OUTPUT STATUS
VIEW PAGER NUMBERS

Input Status

INPUT

/

STATUS

> SENSOR_1 +80.00 DEG

SENSOR_2 ------ DEG
SENSOR_3

SENSOR_4 +79.50 RH

> DEVICE_1 ALARM

DEVICE_2 NORMAL
DEVICE_3 NORMAL

DEVICE_4 NORMAL
DEVICE_5 ALARM
DEVICE_6 EVENT
DEVICE_7 NORMAL
DEVICE_8 NORMAL