Honeywell NXL User Manual

Page 46

Advertising
background image

46(96)

Cabling and connections

Honeywell

Honeywell

Honeywell

Honeywell

6


6.2.5 Control terminal signals

Terminal

Signal

Technical information

1

+10 Vref

Reference voltage

Maximum current 10 mA

2

AI1+

Analogue input,
voltage

(MF4 and bigger: voltage or current)

MF2-MF3: Voltage input
MF4-MF6 Selection V or mA with jumper block X8 (see
page 39):
Default: 0– +10V (Ri = 200 kΩ)

0– 20mA (Ri = 250 Ω)

3

AI1–

Analogue input common

Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND

4

AI2+

Analogue input, voltage or
current

Selection V or mA with jumper block X4(MF2-MF3) and
X13 (MF4-MF6)
Default: 0– 20mA (Ri = 250 Ω)

0– +10V (Ri = 200 kΩ)

5

AI2–

Analogue input common

Differential input;
Allows ±20V differential mode voltage to GND

6

24 Vout

24V auxiliary output voltage

±10%, maximum current 100 mA

7

GND

I/O ground

Ground for reference and controls

8

DIN1

Digital input 1

9

DIN2

Digital input 2

10

DIN3

Digital input 3

R

i

= min. 5kΩ

11

GND

I/O ground

Ground for reference and controls

18

AO1+

Analogue signal (+output)

19

AO1–/GND

Analogue output common

Output signal range:
Current 0(4)–20mA, R

L

max 500Ω or

A

RS 485

Serial bus

Differential receiver/transmitter, bus impedance 120Ω

B

RS 485

Serial bus

Differential receiver/transmitter, bus impedance 120Ω

30

+24V

24V auxiliary input voltage

Control power supply backup

21

RO1/1

22

RO1/2

23

RO1/3

Relay output 1 Switching capacity:

24VDC/8A

250VAC/8A

125VDC/0,4A

Relay output terminals are galvanically isolated from the
I/O ground

Table 6-9. Control I/O terminal signals

NOTE! NXL HVAC additional inputs terminal signals defined in section 11 NXLOPTAI