Honeywell NXL User Manual

Page 66

Advertising
background image

66(96)

Control Keypad

Honeywell

Honeywell

Honeywell

Honeywell

7

17

Motor
underload/
Pump Dry
detection/
Broken belt
Detection

Motor underload protection has tripped.

FAN: check that Belt is not broken
PUMP: check that Pump is not dry

22

EEPROM
checksum fault

Parameter save fault

faulty operation

component failure

Contact the distributor near to you

24

Counter fault

Values displayed on counters are incorrect

25

Microprocessor
watchdog fault

faulty operation

component failure

Reset the fault and restart.
Should the fault re-occur, contact
the distributor near to you.

29

Thermistor fault

The thermistor input of option board has
detected increase of the motor temperature

Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option
board is not in use it has to be short
circuited)

34

Internal bus
communication

Ambient interference or defective hardware

Reset the fault and restart
Should the fault re-occur, contact
the distributor near to you.

35

Application fault

Selected application does not function.

Contact the distributor near to you.

39

Device removed

Option board removed.
Drive removed.

Reset

40

Device unknown Unknown option board or drive.

Contact the distributor near to you.

41

IGBT temperature

IGBT Inverter Bridge overtemperature
protection has detected too high a motor
current.

Check loading.
Check motor size.

44

Device change

Option board changed.
Option board has default settings.

Reset

45

Device added

Option board added.

Reset

50

Analogue input
I

in

<4mA

(selected signal
range 4 to 20
mA)

Current at the analogue input is < 4mA.

control cable is broken or loose

signal source has failed

Check the current loop circuitry.

51

External fault

Digital input fault. Digital input has been
programmed as external fault input and this
input is active.

Check the programming and the
device indicated by the external
fault information. Check also the
cabling of this device.

52

Keypad
communication
fault

The connection between the control keypad
and the frequency converter is broken.

Check keypad connection and
possible keypad cable.

Advertising