Honeywell NXL User Manual

Page 59

Advertising
background image

 

 

 

 

Control Keypad

59(96)

7

Code

Signal name

Unit

ID

Description

V1.1

Output frequency

Hz

1

Frequency to the motor

V1.2

Frequency reference

Hz

25

V1.3

Motor speed

rpm

2

Calculated motor speed

V1.4

Motor current

A

3

Measured motor current

V1.5

Motor torque

%

4

Calculated actual torque/nominal torque of the motor

V1.6

Motor power

%

5

Calculated actual power/nominal power of the motor

V1.7

Motor voltage

V

6

Calculated motor voltage

V1.8

DC-link voltage

V

7

Measured DC-link voltage

V1.9

Unit temperature

ºC

8

Heat sink temperature

V1.10

Analogue input 1

13

AI1

V1.11

Analogue input 2

14

AI2

V1.12

Analogue output
current

mA

26

AO1

V1.13

Analogue output
current 1, expander
board

mA

31

V1.14

Analogue output
current 2, expander
board

mA

32

V1.15

DIN1, DIN2, DIN3

15

Digital input statuses

V1.16

DIE1, DIE2, DIE3

33

I/O expander board: Digital input statuses

V1.17

RO1

34

Relay output 1 status

V1.18

ROE1, ROE2, ROE3

35

I/O exp. board: Relay output statuses

V1.19

DOE 1

36

I/O exp. board: Digital output 1 status

V1.20

PID Reference

%

20

In percent of the maximum process reference

V1.21

PID Actual value

%

21

In percent of the maximum actual value

V1.22

PID Error value

%

22

In percent of the maximum error value

V1.23

PID Output

%

23

In percent of the maximum output value

V1.24

Autochange outputs
1,2,3

30

Used only in Pump and Fan Cascade control

V1.25

Mode

66

Shows the current drive configuration mode selected
with start-up wizard:
0 = No mode selected (Default)
1 = Standard
2 = Fan
3 = Pump
4 = High performance

Table 7-2. Monitored signals