EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51 R0909

8

Safety Features

Frost Protection
If the room temperature falls below 46.4 °F (8 °C), the Excel

10 FCU Controller enables the heating circuit to ensure frost

protection and an alarm is issued. When the temperature

rises above 48.2 °F (9 °C) again, the heating circuit is turned

OFF again.


Smoke Control
The Excel 10 FCU Controller will respond to L

ON

W

ORKS

network emergency commands by switching OFF

heating/cooling outputs and switching OFF the fan

(depressurize) or switching ON the fan at its highest speed

(pressurize). An alarm is issued for any emergency

commands

Fan Failure Protection
When configured with an airflow detector, the Excel 10 FCU

Controller protects equipment by switching OFF heating /

cooling outputs and issuing an alarm when the fan fails.


Fan Interlocks
The Excel 10 FCU Controller can be configured such that

heating and/or cooling outputs are never ON unless the fan is

running. A fan run-up time can be configured to turn ON the

fan prior to the heating/cooling outputs being switched ON,

and a fan overrun time can be configured to keep the fan

running for a period of time after the heating/cooling outputs

are switched OFF.

Operating Modes

The possible modes of operation are listed in Table 4.

Table 4. Modes of operation for Excel 10 FCU Controller

mode

description

events causing a transition to this mode

operational modes (NV reference)
START-UP AND

WAIT

Control algorithms are disabled. Outputs stay in

their initial positions. Physical inputs are periodically

read and digital filtering of analog inputs is turned

OFF to speed up settling time. Input NVs are

received and output NVs are sent periodically.

This is the first mode after an application restart.

FLOATING

OUTPUTS SYNCH

The Excel 10 FCU Controller drives the floating

control valves to their initial positions and then

transitions to one of the control modes.

When the effective occupancy changes to

"unoccupied" or "standby", after start-up, after 24

hours since the last positioning, or after each

positioning to 0%, the Excel 10 FCU Controller

transitions to this mode.

COOLING

The Excel 10 FCU Controller is controlling in the

cooling mode.

Network input nviApplicMode has a value of

HVAC_COOL or HVAC_AUTO and the space

temperature is above the cooling setpoint.

HEATING

The Excel 10 FCU Controller is controlling in the

heating mode.

Network input nviApplicMode has the value of

HVAC_HEAT or HVAC_AUTO and the space

temperature is below the heating setpoint.

MANUAL MODE

The control algorithms stay active and outputs are

controlled automatically until set individually to test

positions using the input NV nviTest.

Network input nviManualMode has value of

MODE_MANUAL.

FACTORY TEST

Control algorithm is disabled; a special factory test

program runs.

This mode is for factory testing, only.

DISABLED Control

algorithms

are terminated, outputs are

turned OFF (turn-OFF sequences and interlocks are

active). Frost protection is disabled.

Network input nviManualMode has a value of

MODE_DISABLED.

PRESSURIZE Heating/cooling

outputs are switched OFF, and the

fan is switched ON at its highest speed.

Network input nviEmerg containing smoke control

signal from the L

ON

W

ORKS

network has the value

of EMERG_PRESSURIZE.

DEPRESSURIZE

Heating, cooling, and fan outputs are switched OFF. Network input nviEmerg containing smoke control

signal from the L

ON

W

ORKS

network has the value

of EMERG_DEPRESSURIZE.