EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51 R0909

58

Table C4. Output Variables for Excel 10 FCU Controllers.

NV name

field name

engineering units:

English (metric) or states plus

range

digital

state

or

value

default comments

nvoFcuStatus



normal operating modes, such as CTL_COOL. When the effective
occupancy changes to unoccupied or 24 hours have elapsed since
the last start-up or CTL_FLOATING_OUT_SYNCH mode, the
controller enters this mode again to reset the floating output
position tracking.
CTL_START_UP_WAIT is the first mode after an application
restart. No control algorithms are active, and heat/cool outputs stay
in their default positions. CTL_FLOATING_OUT_SYNCH follows.
CTL_DISABLED disables heat/cool control.

nvoFcuStatus

alarm_type

Same as nvoAlarm.type

This output variable is the latest alarm detected by the node (if
any) and has the same value as nvoAlarm.type.

nvoFcuStatus dlc_shed

Bit
NOT ACTICE
ACTIVE


0
1

This output variable indicates the state of the demand limit control.

nvoFcuStatus eff_window_open

Bit
CLOSED or NOT_ASSIGNED
OPEN


0
1

This output variable indicates the real status of the window
detection, either from the digital input or from the network.

nvoFcuStatus hw_window_open

Bit
CLOSED or NOT_ASSIGNED
OPEN


0
1

This output variable indicates the status of the digital input
configured as a window contact.

nvoFcuStatus fan_feedback Bit

FAN_OFF_AFTER_ON_CMD
FAN_RUNS


0
1

This output variable indicates the status of the fan when the digital
input is configured for an air flow sensor.

nvoFcuStatus external_active Bit

EXTERNAL_NOT_ACTICE
EXTERNAL_ACTIVE


0
1

This output variable applies to nciFcuConfig.reheat_config =
EXTERNAL only and indicates the state of the relay.

nvoFcuStatus fan_stages_active

UBYTE
F_OFF
F_SPEED1
F_SPEED2
F_SPEED3
F_NO_FAN


0
1
2
3
255

When the controller is configured for one or more fan stages, this
output variable reports the current fan stage active.



nvoFcuStatus output_position[0]

SNVT_lev_percent
0 to 100%
163.835% = INVALID

This output variable indicates the position of the output 1.

nvoFcuStatus output_position[1]

SNVT_lev_percent

This output variable indicates the position of the output 2.