EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

11

Controller Performance Specifications

Power:
W7752D and W7752E; W7754K,M,N,P

230 Vac +10%, -15%, 50/60 Hz.

W7752F and W7752G

115 Vac +10%, -15%, 50/60 Hz.

W7752J

100 Vac

±6%, 50/60 Hz.

W7754L

24 Vac

±20%, 50/60 Hz.


Operating Temperature:

32...122°F (0...50°C).


Shipping/Storage Temperature:

-40...+158°F (-40...+70°C).


Relative Humidity:

5% to 95% non-condensing


Inputs:
Temperature Sensor:

20k ohm NTC

Setpoint Potentiometer:

10k ohm


Digital Input:

Closed

≤ 400 ohms

Open

≥ 10 K ohms


Outputs:
Triac voltage range:

24 Vac ± 20%.

Triac max. current ratings:

250 mA continuous

650 mA surge for 30 sec.

IMPORTANT:

When any device is energized by a triac, the device

must be able to sink a minimum of 15 mA. If non-

Honeywell motors, actuators, or transducers are to

be used with Excel 10 FCU Controllers, compatibility

must be verified.

Fan relays voltage range:

20 to 253 Vac

Fan relays max. current rating:

3 A

Electric reheat relay voltage range:

20 to 253 Vac

Electric reheat relay max. current rating:

10 A

6 A (UL916)

Interoperability
The Excel 10 FCU Controllers use the LonTalk protocol. They

support the L

ON

M

ARK

Functional Profile # 8020 “Fan Coil Unit

Controller”, version 2.0. Fig. 8 shows the implementation

used.

Hardware

Output

Fan Coil Unit Controller
Object #8020

Mandatory
Network
Variables

Manufacturer

Defined

Section

Optional
Network
Variables

Configuration Properties

nv10

nviWaterTemp
SNVT_temp_p

nv9

nviSetPtOffset
SNVT_temp_p

nv8

nviApplicMode
SNVT_hvac_mode

nv7

nviOccCmd
SNVT_occupancy

nv6

nviFanSpeedCmd
SNVT_switch

nv16

nvoEffectSetPt
SNVT_temp_p

nv15

nvoSpaceTemp
SNVT_temp_p

nv14

nvoReheat
SNVT_switch

nv13

nvoDischAirTemp
SNVT_temp_p

nv12

nvoLoadAbs
SNVT_power

nv11

nvoTerminalLoad
SNVT_lev_percent

nv2

nviSetPoint
SNVT_temp_p

nv1

nviSpaceTemp
SNVT_temp_p

nv5

nvoFanSpeed
SNVT_switch

nv4

nvoCoolOutput
SNVT_lev_percent

nv3

nvoHeatOutput
SNVT_lev_percent

nv19

nv17

nvoEffectOcc
SNVT_occupancy

nviDischAirTemp
SNVT_temp_p

nvoEnergyHoldOff
SNVT_switch

nv18

nviEnergyHoldOff
SNVT_switch

nc49 - nciSndHrtBt

SNVT_time_sec

mandatory

nc52 - nciMinOutTm

SNVT_time_sec

optional

nc48 - nciRcvHrtBt

SNVT_time_sec

optional

nc17 - nciLocation

SNVT_str_asc

optional

nc60 - nciSetPnts
nc59 - nciNumValve

SNVT_temp_setpt
SNVT_count

mandatory
optional

Hardware

NOT SUPPORTED.

Input

nv20

nv21

nvoUnitStatus
SNVT_hvac_status

nvoSensorOcc
SNVT_occupancy

nvoDigitInState
SNVT_switch

nviSensorOcc
SNVT_Occupancy

nviEmerg
SNVT_hvac_emerg

nviReheatRelay
SNVT_switch

Fig. 8. L

ON

M

ARK

FCU object profile