EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

47 EN2B-0285GE51

R0909

Table C3. Input Variables for Excel 10 FCU Controllers

NV name

field name

engineering units:

English (metric) or states plus

range

digital

state

or

value

default comments

nviApplicMode

SNVT_hvac_mode
HVAC_AUTO
HVAC_HEAT
HVAC_COOL
HVAC_OFF
HVAC_NUL


0
1
3
6
255

HVAC_AUTO
(if bound but fails to be
received or at application
restart)

This input variable coordinates the controller operation with the
main equipment controller. Depending upon the available supply
energy, the main equipment controller commands the Fan Coil
Unit controller to operate in heat mode only, cool mode only or
heat and cool mode if appropriate to the configuration.
HVAC_AUTO means that both heating and cooling equipment are
available, and the current mode is determined by the control
algorithm depending upon the room temperature and effective
setpoint. HVAC_AUTO is invalid for changeover applications.
When the Digital input is configured for Heat/Cool changeover
input, this input will always have priority over the network
nviApplicMode’s HVAC_HEAT or HVAC_COOL.

nviDlcShed

BYTE
NORMAL
SETPOINT_SHIFT


0
1

0 (if bound but fails to be
received or at application
restart)

This input variable is from an energy management system. When
it is 0, the temperature control algorithm operates in a normal
mode. When it is 1, the effective setpoint will be shifted by the
amount defined in nciEmergyManag.si_dlc_setpt_bump. For
cooling the effective setpoint will be increased, for heating the
effective setpoint will be decreased always with regard to the frost
protection limit.

nviEmerg

SNVT_hvac_emerg
EMERG_NORMAL
EMERG_PRESSURIZE
EMERG_DEPRESSURIZE
EMERG_PURGE
EMERG_SHUTDOWN
EMERG_NUL


0
1
2
3
4
255

EMERG_NORMAL
(at application restart)

This input variable is an emergency input from a device that
determines the correct action during a given emergency (such as
a fire).
• EMERG_NORMAL, EMERG_NUL: terminate EMERG_

commands and restores the control algorithm.

• EMERG_PRESSURIZE,

EMERG_PURGE,

EMERG_SHUTDOWN: heat/cool outputs OFF, fan ON at
highest speed.

• EMERG_DEPRESSURIZE: heat/cool outputs OFF, fan OFF.

nviFanSpeedCmd value

SNVT_switch
0 to 100%

100%

(at application restart)

This input variable allows control of the fan speed by another
node, such as another Fan Coil Unit Controller acting as a master
in a master/slave relationship.

nviFanSpeedCmd state

SNVT_switch
OFF
ON
NUL


0
1
255

NUL
(at application restart)

See above.

nviInUse

UWORD
0 to 65535

0 (if bound but fails to be
received), 65535 ( for 60s
at application restart)

This input variable is used by the engineering tool or other
supervisory node that it is "logged on" to the controller node. It
should be set every minute, or the controller will reset it after 60s
to automatically log off the supervisory node.