EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

15

Excel 10 Wall Module Options

A typical FCU installation will include an Excel 10 wall module

containing a 20k ohm NTC room temperature sensor and

additional features depending on the wall module type (see

Excel 10 wall module literature for further information).

Excel 10 FCU Controllers can use a return air sensor rather

than the sensor in the wall module if it is wired to the wall

module sensor input. Setpoint adjustments can be configured

as relative or absolute, and upper and lower limits can be set.

A configuration option for the fan speed switch allows it to be

disabled if not required. The bypass button can be configured

to override the control mode to "occupied" for a configurable

bypass time and to override the control mode to "unoccupied"

for an indefinite time, or it may be configured to only override

to "occupied". The button may also be used to cancel the

override.

Common Temperature Control (Master/Slave Controllers)
When one or more Excel 10 FCU Controllers serve a

common area and a single temperature sensor is to be used,

a master/slave arrangement can be configured. One Excel 10

FCU Controller is configured for the local wall module with the

desired options. The other Excel 10 FCU Controller(s) will be

configured without wall modules and with certain network

variables bound with the master controller. Refer to

Application Step 6 of this document for more details.

IMPORTANT

The slave units must have the same HVAC

equipment connected to it as the master units.

The slave units will not use any internal temperature

setpoints or control algorithms. The master controller

determines heating/cooling output based upon

setpoints and occupancy and L

ON

W

ORKS

network

command mode status and communicates this to the

slave via the L

ON

W

ORKS

network.