EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

3

Control Application

Fan coil unit systems in commercial buildings control room

temperature through the control of heat and/or cold water

valves and fan speed. Electric reheat coils may also be used

in the system. The Excel 10 FCU Controller is located in the

FCU and is typically connected to an Excel 10 wall module

which incorporates a temperature sensor, setpoint and fan

speed controls, and a bypass or override button. Fig. 2 shows

a typical FCU ontrol application.

LonWorks network

e.g. Excel 10 W7754

FCU Controller

window

contact

Excel 10

wall module

Honeywell

D-71101 Schönaich

Made in Germany

Fig. 2. Typical Fan Coil Unit control application

Control Provided

Excel 10 FCU Controllers provide room temperature control

for two- and four-pipe fan coil units with optional electric

heating coil. The basic control sequence is shown in Fig. 3.

As space temperature falls below the heating setpoint, the

heating output is increased. As space temperature

increases above the cooling setpoint, the cooling output is

modulated to 100%. Switching levels for staged

heating/cooling and fan speeds are configurable. The fan

may still be configured to run continuously during the zero

energy band in the "occupied" mode. Additional

configurable fan control features include fan minimum

ON/OFF times, run-up, and overrun-times.

Excel 10 FCU Controllers use a PID control algorithm in

which each of the three parameters can be configured.

There are additional configurable boost parameters ("PID

Boost:" "Cooling" and "Heating") which specify a range

outside of which the heating or cooling outputs are turned

ON fully for faster response (in the case of thermal

actuators, this specifies the control hysteresis). The

controllers are delivered with factory defaults for each of the

parameters.