EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

5

Table 1. Example setpoint values based upon default configuration – "absolute middle" setpoint knob (°C)

occupancy

mode

configured

cooling setpoint

configured

heating setpoint

ZEB

setpoint

knob

1

effective cooling

setpoint

2,3

effective heating

setpoint

2,4

"occupied" 23 21

2

21 22

20

"standby" 25 19

6

21 24 18

"unoccupied" 28

16 12

X

28

16

NOTES:
1. Sample value shown. Limited by default configuration settings to the range of 12...30°C.
2. Limited to the range of 10...35°C.
3. = setpoint knob + (ZEB/2)
4. = setpoint knob – (ZEB/2)

Table 2. Example setpoint values based upon default configuration - Relative setpoint knob (°C)

occupancy

mode

configured

cooling setpoint

configured

heating setpoint

ZEB

setpoint

knob

1

effective cooling

setpoint

2,3

effective heating

setpoint

2,4

"occupied" 23 21

2

-2 21

19

"standby" 25 19

6

-2 23 17

"unoccupied" 28

16 12

X

28

16

NOTES:
1. Sample value shown. Limited by default configuration settings to the range of -5...+5°C.
2. Limited to the range of 10...35°C.
3. = configured cooling setpoint + setpoint knob
4. = configured heating setpoint + setpoint knob