EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51 R0909

32

Broadcasting the Service Message

The Service Message allows a device on the LonWorks

network to be positively identified. The Service Message

contains the controller Neuron ID number and, therefore, can

be used to confirm the physical location of a particular Excel

10 FCU Controller in a building.

When an Assign Neuron ID command is issued from the LNS

tool, the node goes into the SERVICE_MESSAGE mode for

one minute. In the SERVICE_MESSAGE mode, pressing the

occupancy override button on the remote Excel 10 wall

module causes the Service Message to be broadcast on the

network. All other functions are normal in the

SERVICE_MESSAGE mode. If an FCU Controller does not

have a bypass button connected, it can still broadcast the

Service Message on the network by temporarily shorting the

controller Fan Speed/Bypass input terminal to the AGND

terminal on the controller (terminals 5 and 7) with the

controller in SERVICE_MESSAGE mode.

Manual Mode

The FCU Controller can be put into a manual mode which

allows manual setting of outputs for system checkout. The

variable nviManualMode must be set to Mode_Manual using

the LNS tool. Triac outputs can be set to any combination of

ON/OFF or can be set to a test position based upon the

configured valve runtime/cycle time. The fan relays and

reheat relay (W7752D, F and W7754P1000, only) can also be

commanded ON/OFF in any combination. The override LED

can be commanded ON/OFF in this mode also.