EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51 R0909

52

Table C3. Input Variables for Excel 10 FCU Controllers

NV name

field name

engineering units:

English (metric) or states plus

range

digital

state

or

value

default comments

nviWindow value

SNVT_switch.value
0 to 100%



0 (if bound but fails to be
received or at application
restart)

This input variable allows a window contact node or another
controller to be used as remote window contact. More than one
nvoWindow may be bound to one nviWindow, which allows one
node to be used to handle several distributed window contacts. In
this case the control process assumes an open window if at least
one bound window node detects an open window. ‘Window
Closed’ would be assumed if all nvoWindows bound to nviWindow
indicate the window being closed for at least the failure detect time
(nciSndHrtBt).

nviWindow state

SNVT_switch.state
CLOSED
OPEN
NO_WINDOW


0
1
255

NO_WINDOW
(if bound but fails to be
received or at application
restart)

See above.