Setpoints – Honeywell EXCEL 10 W7752D User Manual

Page 6

Advertising
background image

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51 R0909

4

Fig. 3. Control sequence diagram

Setpoints

Setpoint Knob
The Excel 10 FCU Controllers may be hardwired to an Excel

10 wall module equipped with a setpoint knob. When the

Excel 10 FCU Controller has been configured (using the LNS

plug-in tool) to read input from the wall module's setpoint

knob, the value from the setpoint knob is used to calculate the

"occupied" setpoint for the heating and the cooling modes.

There are two configurations which determine how the

setpoint used by the control algorithm is calculated: "relative"

(or "offset") and "absolute middle". When configured for

"relative", the Excel 10 wall module setpoint knob represents

a number from -9...+9 DDF(-5...+5 K) which is added to the

configured "occupied" and "standby" setpoints for the heating

and the cooling modes. When configured to "absolute

middle", the setpoint knob becomes the mid-point of the Zero

Energy Band (ZEB) extending between the "occupied" or

"standby" setpoints for the heating and the cooling modes.

The range of the ZEB is found by taking the difference

between the "occupied" or "standby" setpoints configured for

the heating and the cooling modes; in the case of "absolute

middle", the current "occupied" and "standby" setpoints are

therefore found as follows:

When the Excel 10 FCU Controller is in the "occupied" mode:

nvoActiveSetPt (in cooling mode) =

nvoSensor.remote_set_point + (Cooling Occupied

Setpoint - Heating Occupied Setpoint) / 2

nvoActiveSetPt (in heating mode) =

nvoSensor.remote_set_point - (Cooling Occupied

Setpoint - Heating Occupied Setpoint) / 2

for Standby:

nvoActiveSetPt (in cooling mode) =

nvoSensor.remote_set_point + (Cooling Standby

Setpoint - Heating Standby Setpoint) / 2

nvoActiveSetPt (in heating mode) =

nvoSensor.remote_set_point - (Cooling Standby

Setpoint - Heating Standby Setpoint) / 2

When the Excel 10 FCU Controller is in the "unoccupied"

mode, the remote setpoint knob is ignored, and the con-

figured setpoints for this mode are used instead.


Setpoint Limits
Setpoints are limited to the range of 50...95°F (10...35°C).

The value of the setpoint knob is limited to the range provided

by the configuration parameters Maximum Limit Setpoint pot

and Minimum Limit Setpoint pot. In the case of absolute

"occupied" and "standby" setpoints, the setpoint knob still

represents the mid-point of the ZEB, even when set to either

of these limits. The actual setpoints are given by the

equations shown above. When the setpoint knob is configured

to be "relative", the lowest actual "occupied" setpoint allowed

is equal to SptHeatOcc - SptKnobLowLim, and the highest

allowed is equal to SptCoolOcc + SptKnobHiLim. The lowest

and highest "standby" setpoints are found in an analogous

fashion.


Setpoint from Network
When the Excel 10 FCU Controller is not configured to be

hardwired to a wall module, nviSetPoint must be bound to

another node that provides a setpoint. When bound and when

a valid update is received, nviSetPoint is used with the

appropriate ZEB:

ZEBoccupied = Cooling Occupied Septoint - Heating

Occupied Setpoint

ZEBstandby = Cooling Standby Setpoint - Heating

Standby Setpoint

The "unoccupied" setpoint does not depend on nviSetPoint at

all.


Setpoint Offset
Third-party nodes may be bound to nviSetPtOffset to shift the

setpoint in the range of -18 to 18 DDF (-10 K to 10 K).

Advertising