Step 4. prepare wiring diagrams, Power wiring, General considerations – Honeywell EXCEL 10 W7752D User Manual

Page 21

Advertising
background image

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

19

Fig. 15. Free topology L

ON

W

ORKS

layout examples

NOTE: See section "L

ON

W

ORKS

Termination" on page 23 for

additional details.

IMPORTANT

Notes on Communications Wiring:

• All field wiring must conform to local codes and

ordinances.

• Do not use different wire types or gauges on the

same L

ON

W

ORKS

segment. The step change in

line impedance characteristics would cause

unpredictable reflections on the L

ON

W

ORKS

net-

work. When using different types is unavoidable,

use a Q7751A Router at the junction.

• Do not use shielded cable for L

ON

W

ORKS

wiring

runs. The higher capacitance of the shielded

cable will cause degradation of communications

throughput. In noisy (high EMI) environments,

avoid wire runs parallel to noisy power cables, or

lines containing lighting dimmer switches, and

keep at least 3 in. (76 mm) of separation between

noisy lines and the L

ON

W

ORKS

cable.

• Make sure that neither of the L

ON

W

ORKS

wires is

grounded.

Power Wiring

IMPORTANT

Notes on Power Wiring:

All field wiring must conform to local codes and

ordinances.

See Table 10 for permitted wire sizes.

To minimize EMI noise, do not run Triac and/or

relay output wires in the same conduit as the

input wires or the L

ON

W

ORKS

communications

loop.

To comply with CE requirements, in the case of

devices having a voltage range of 50 to 1000 Vac

or 75 and 1500 Vdc which are not provided with a

supply cord and a plug or with other means for

disconnection from the supply having a contact

separation of at least 3 mm in all poles, the

means for disconnection must be incorporated in

the fixed wiring.

Step 4. Prepare Wiring Diagrams

General Considerations

The purpose of this step is to assist the application engineer

in developing job drawings to meet job specifications.

NOTE: For field wiring, when two or more wires are to be

attached to the same connector block terminal, be

sure to twist them together. Deviation from this rule

can result in improper electrical contact.

Table 10 lists wiring types, sizes, and length restrictions for

Excel 10 FCU Controller products.