EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51 R0909

62

Table C4. Output Variables for Excel 10 FCU Controllers.

NV name

field name

engineering units:

English (metric) or states plus

range

digital

state

or

value

default comments

nviSpaceTemp is bound to another node, nvoSpaceTemp is not
reported on the network.

nvoStatus object_id

UWORD
NODE_OBJECT
FCU_OBJECT


0
1

This output variable belongs to the Node Object and reports the
status for any object on a node. This is the answer to the
nviRequest.

nvoStatus invalid_id

Bit
VALID_ID
INVALID_ID


0
1

This output variable indicates whether nviRequest uses a fault
object ID.

nvoStatus invalid_request

Bit
VALID_REQUEST
INVALID_REQUEST


0
1

This output variable indicates whether nviRequest uses a fault
request.

nvoStatus disabled

Bit
ENABLED
DISABLED


0
1

This output variable indicates whether the device is enabled or
disabled (nviManualMode = DISABLE).

nvoStatus comm_failure

Bit
COMMUNICATION_OK
COMMUNICATION_FAILURE


0
1

This output variable indicates whether an update nviRcvHrtBt is
missing.

nvoStatus in_alarm

Bit
NO_ALARM
IN_ALARM


0
1

This output variable indicates whether an alarm occured. See
nvoAlarm.

nvoStatus report_mask Bit

NO_REPORT_MASK
REPORT_MASK


0
1

This output variable shows the answer to nviRequest >
REPORT_MASK

nvoTerminalLoad

SNVT_lev_percent
-163..163%
163.835% = INVALID


This output variable shows the terminal load, which is a percentage
between -160% and +160% based upon the control output level.
Negative values indicate heating load and positive values indicate
cooling load. 100% is the full terminal capacity. An absolute
terminal load value of more than 100% indicate that the terminal is
not able to supply the required heating or cooling energy which at
the zone controller should cause a demand for more supply
energy. nvoHeatOutput will be transmitted immediately when its
value has changed significantly (>= 1%).

nvoUnitStatus mode

SNVT_hvac_mode
HVAC_HEAT
HVAC_COOL
HVAC_OFF


1
3
6

This output variable reports the last operating mode of the control
algorithm. It is not set to HVAC_OFF if the Heating and Cooling
Output shows 0%. HVAC_OFF is set when the Device is disabled
from nviRequest, nviManualMode or nviApplicMode.