EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

37 EN2B-0285GE51

R0909

Table C2. Configuration Variables for Excel 10 FCU Controllers

NV name

field name

engineering units:

English (metric) or states

plus range

digital

state

or

value

default comments

nciApplVer

application_type

UBYTE, 0 to 255

0

This configuration variable specifies the current application number of
the Excel 10 application.

nciApplVer

version_no

UBYTE, 0 to 255

0

This configuration variable specifies the version number of the Excel
10 application.

nciApplVer

time[0]

UBYTE, 0 to 255

0

The time stamp of the last change to the Excel 10 application con-
figuration. Time meets the ANSI C time stamp requirement specifying
the number of seconds elapsed since midnight (0:00:00), January 1,
1970. It is represented in the Intel Format and is four bytes in length.

nciApplVer

time[1]

UBYTE, 0 to 255

0

See above.

nciApplVer

time[2]

UBYTE, 0 to 255

0

See above.

nciApplVer

time[3]

UBYTE, 0 to 255

0

See above.

nciDeviceName

ch[0-17]

UBYTE, 0 to 255

0

This configuration variable specifies the name of each device. This is
an ASCII string with the a size of 18 characters. A name with all NULLs
means that the device has not been configured.

nciLocation

SNVT_str_asc

0x00

This configuration variable is used to provide more descriptive physical
loacation information than can be provided by the Neuron chip's 6 byte
location string.

nciMaxSendTime

SNVT_temp_p
0 to 6553 seconds

0 s from factory

This configuration variable specifies the maximum time that expires
before the node object automatically transmits nvoStatus. This pro-
vides a heartbeat output that can be used by the destination objects to
ensure that the node is still healthy. The heartbeat output may be
disabled by setting nciMaxSendTime = 0.