EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

23

Table 14. Output assignments of Excel 10 W7754 FCU Controller for various actuator types

OUT1

OUT2

output type

stage

19

20

21

22

floating

-- close open close open

0 -- OFF -- OFF

1-stage

1 -- ON -- ON
0 OFF OFF OFF OFF
1 OFF ON OFF ON

2-stage

2 ON OFF ON OFF
0 OFF OFF OFF OFF
1 OFF ON OFF ON
2 ON OFF ON OFF

3-stage

3 ON ON ON ON

PWM

-- -- PWM -- PWM

thermal

--

-- ON/OFF -- ON/OFF

L

ON

W

ORKS

Termination

One or two L

ON

W

ORKS

terminations are required, depending

on the given LonWorks bus layout.

Double termination is required only when the network is a

daisy-chain configuration and the total wire length is greater

than 1640 ft (500 m). The max. lengths described in Step 2

must be adhered to for either a daisy chain or free topology

L

ON

W

ORKS

layout. See Fig. 17 for connection details for a

doubly terminated bus. See Fig. 18 for connection details for

a singly terminated bus.

Two different L

ON

W

ORKS

termination modules are available:

L

ON

W

ORKS

termination module, order no.:

209541B

L

ON

W

ORKS

connection / termination module (mountable

on DIN rails and in fuse boxes), order no.:

XAL-Term

3

4

L

O
N

Honeywell

XAL-Term

L

O
N

removable screw-type

3-pole terminal block

1

5

3

4

0

6

shield

shield

LON

Termination

FTT/LPT Bus

FTT/LPT Free

Park Position

plug-in

jumper

Fig. 16. L

ON

W

ORKS

connection and termination module


NOTE: The Q7750A Zone Manager has an internal ter-

mination circuit, although jumpers are required at the
terminal block to connect it. See form number 95-
7509 for details.

Fig. 17. Termination Module connections for a doubly-

terminated FTT network

Fig. 18. Termination Module connections for a singly-

terminated FTT network