EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

EN2B-0285GE51

R0909

27

Input

The available options for input configurations with the default values shown are listed in Table 17. See sections "Control

Provided" and "Configurations" above for more information on parameters.

Table 17. FCU Controller input configuration options

function

configuration options

default

space temperature sensor

no sensor

sensor

sensor

bypass button

none - bypass button is disabled.
bypass unoccupied - bypass button overrides current mode to occupied

for configurable bypass time for button press of 1.1 to 4 seconds (single

press with T7560) or permanently overrides to unoccupied for button

press of 4.1 to 7 seconds (more than 5 seconds with T7560).
bypass - bypass button only overrides current mode to occupied and to

cancel the override again.

bypass unoccupied

LED/LCD

LED override - shows override from bypass button or from network.
LED occupancy - shows effective occupancy mode.
LCD display - only used with T7560 Wall Modules; occupancy mode is

represented by different symbols.

LED override

fan speed switch

(or respective T7560

setting)

no switch

3-position switch

4-position switch

5-position switch

5-position switch

setpoint knob

no knob

relative

absolute middle

relative

min. limit setpoint pot

limit for setpoint knob in either degrees F (absolute setpoint, 53.6 to 86

°F) or DDF (relative setpoint, -9 to 9 DDF)
(limit for setpoint knob in either degrees C (absolute setpoint, 12 to

30°C) or K (relative setpoint, -5 to 5 K))

-9 DDF (53.6 °F for

absolute setpoint)
(-5 K (12 °C for

absolute setpoint))

max. limit septoint pot

limit for setpoint knob in either degrees F (absolute setpoint, 53.6 to 86

°F) or DDF (relative setpoint, -9 to 9 DDF)
(limit for setpoint knob in either degrees C (absolute setpoint, 12 to 30

°C) or K (relative setpoint, -5 to 5 K))

9 DDF (86 °F for

absolute setpoint)
(5 K (30 °C for

absolute setpoint))

digital input

not used

window closed

occupied sensor

cool changeover

window open

unoccupied sensor

heat changeover

movement

no movement

not used

Notes:
1. The temperature sensor option no sensor requires that either the FCU Controller be configured as a slave unit receiving

heating and cooling control levels from the master unit via the network, or that it receive temperature information over the

network from another device.

2. The digital input option to be selected is the condition in which the input will be high (switch contact closed).

3. Furthermore, all W7754 controllers are equipped with an additional digital output which is permanently assigned to the

function window contact. This digital input is not visible in the configuration with the plug-in. This digital input can be enabled /

disabled using the right DIP switch located on the top of the controller