EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

43 EN2B-0285GE51

R0909

Table C2. Configuration Variables for Excel 10 FCU Controllers

NV name

field name

engineering units:

English (metric) or states

plus range

digital

state

or

value

default comments

nciFcuConfig cycle_time[0]

SNVT_time_sec
0 to 1200s for stage output
0 to 600s for floating output
20 to 600s for PWM output

150 s for floating

This configuration variable specifies for the output 1 configured as
• FLOATING: the runtime of the valve (time to run from fully closed to

fully open)

• PWM: the cycle time
• ONE_STAGE, TWO_STAGE, and THREE_STAGE: minimum ON

time before switching to the next stage.

nciFcuConfig cycle_time[1]

SNVT_time_sec
0 to 1200s for stage output
0 to 600s for floating output
20 to 600s for PWM output

150 s for floating

This configuration variable specifies for the output 2 configured as
• FLOATING: the runtime of the valve (time to run from fully closed to

fully open)

• PWM: the cycle time
• ONE_STAGE, TWO_STAGE, and THREE_STAGE: minimum ON

time before switching to the next stage.

nciFcuConfig min_stage_off_time[0]

SNVT_time_sec
0 to 600 seconds

90 s

This configuration variable is used only for ONE_STAGE,
TWO_STAGE, and THREE_STAGE output 1 and specifies the mini-
mum OFF time before switching to the next stage.

nciFcuConfig min_stage_off_time[1]

SNVT_time_sec
0 to 600 seconds

90 s

This configuration variable is used only for ONE_STAGE,
TWO_STAGE, and THREE_STAGE output 2 and specifies the mini-
mum OFF time before switching to the next stage

nciFcuConfig reheat_config

BYTE
REHEAT
FREE_USE
REL_NOT_USED


0
1
255

REHEAT

This configuration variable specifies the usage of the reheat relay.
FREE_USE specifies that the relay is controlled via the network using
the nviReheatRelay .

nciFcuConfig PwmZeroPosn SNVT_lev_percent

0 to 100%

0%

This configuration variable specifies the zero position for PWM
actuators. This setting applies to PWM actuators only and is used for
both actuators if both are configured as PWM actuators.

nciFcuConfig PwmFullPosn

SNVT_lev_percent
0 to 100%

100%

This configuration variable specifies the fully open position for PWM
actuators. This setting applies to PWM actuators only and is used for
both actuators if both are configured as PWM actuators.

nciFcuGains si_pid_Xp[0]

SNVT_temp_p
2.25 to 180 DDF
(1.25 to 100 K), 0 = Disable

36 DDF (20 K)

This configuration variable specifies the throttling range for use in the
proportional portion of the PID loop gain for the cooling mode. The
minimum configurable value (not including 0 for disabling) is 3.6 DDF
(2 K) for PI or 2.25 DDF (1.25 K) for P control. For versions prior to
1.0.3, the minimum value is 7.2 DDF (4 K).