3 system setup menu, 1 output setup menu, Advanced operations – Hach sc1000 User Manual

Page 80

Advertising
background image

78

Advanced Operations

6.3 System setup menu

The system setup menu contains the main configuration settings for the sc1000
controller.

The system setup menu can include following items:

OUTPUT SETUP

CURRENT INPUTS

RELAY

NETWORK MODULES

GSM-MODULE

DEVICE MANAGEMENT

DISPLAY SETTINGS

BROWSER ACCESS

STORAGE CARD

SECURITY SETUP

The availability of the menu items depends on the installed internal plug-in expansion
cards or external DIN rail modules.

6.3.1 Output setup menu

Note: This menu appears only if an output card is installed in the sc1000 controller.

The content of the output setup menu depends on the selected use/working mode:
Linear/Control or PID Control. The current output card can be used with the output
current linearly dependent to a process value or with the output current working as a PID
controller.

LINEAR CONTROL
In this working mode the output current is linearly dependent to a process value after it
has been processed by the internal formula parser (if prompted).

PID CONTROL
In this working mode the current output module generates a current output which tries to
control the process value. The PID controller controls the process value to be equal to
the set point when a disturbance changes the value of the process value or a new set
point is set.

The output current can be in a working range of 0

20 mA or 4

20 mA. The highest output

current is 22 mA. If necessary adjust the output current with an offset and a correction
factor to enhance the accuracy. By default these two parameters are set to “0” (offset)
and “1” (correction factor).

Advertising