83

Advanced Operations

6.3.2 Current inputs menu

Note: The menus appear only if an input card is installed in the sc1000 controller.

The current input card can be used as an analog input card to measure an input current
in a range from 0

20 mA or 4

20 mA or it can be used as an digital input card. The

current input menu content depends on its use:

ANALOG CURRENT INPUT
The current input card connects devices with a current input interface to the sc1000
controller. Every current input channel can be configured separately, unit and parameter
are displayed in the measured value display. It is mandatory to have an corresponding
open jumper on the current input card to connect a device.

DIGITAL CURRENT INPUT
To differ two digital states the corresponding jumper on the internal current input card has
to be closed respectively the corresponding bridge has to be set at the external current
input card. The different states are recognized by closing or opening a contact between
the corresponding screwing terminals.

There is the possibility to adjust the input current measuring with an offset and a
correction factor to enhance the accuracy. By default these two parameters are set to “0”
(offset) and “1” (correction factor). When a channel is used as a digital input the display
will show the values “HIGH” or “LOW”.

SYSTEM SETUP
CURRENT INPUTS
mA INPUT INT/EXT

Select INPUT card 1,2,3 or 4

EDIT NAME

Default value: Serial number of device as text
Enter text for example for the location of the current source.

DEVICE NAME

Default value: No text
Sets the device name.

PARAMETER NAME

Default value: No text
Sets the parameter name.

SET PARAMETER

Default value: “ChanX” (X=Channel number of the input current module)
Sets parameter for the calculated output value.

DATA VIEW

Default value: OUTPUT VALUE
Sets the value which is displayed as the measured value in the display module and logged into
the data logger.

INPUT CURRENT

Displays the real measured input current.

OUTPUT VALUE

Displays the calculated output value after scaling the output value with the SET LOW VALUE
and SET HIGH VALUE menu settings.

UNIT

Default value: No text
Sets the unit for the calculated output value.

SET FUNCTION

Default value: ANALOG

ANALOG

Input channel is used as analog input.

DIGITAL

Input channel is used as digital input.

SET FILTER

Default value: 10 seconds
Sets a period of time for recording measured input currents.
The input current is the result of an average value, calculated from the last measured input
currents recorded over a defined period (which is set in this menu).