Advanced Operations

Figure 57

-

Figure 59

show the behavior of the relay in the 2 Point Control function under

different conditions.

MIN TIMER EXPIRE

Default value: 0 seconds (off)
Indicates a period of time (in seconds) for the release of the OnMin TIMER and the OffMin
TIMER.
Relay turned on, OnMin TIMER activated: Displays the time left before the relay can be turned
OFF again.
Relay turned off, OffMax TIMER activated: Displays the time left before the relay can be turned
ON again.

2 POINT CONTROL

Figure 57 Relay behavior—2 POINT Control mode (without delay)

1

High Alarm

4

OffMax-time

2

Low Alarm

5

OnMax-time

3

Time (x-axis)

6

Source (y-axis)

Table 30 Color/line code for

Figure 57

Selected Source
Relay contact (phase high)