3. In

the

Send Trap for Alarms of Group section, you determine which alarms will be sent as SNMP traps to

each manager. In each manager column, select the alarm types you want to include for that manager.

4. In

the

Trap Options area, select Standard traps include serial number if you want trap messages to include

the IDU serial number.

Select Report local traps of far end IDU if you want remote IDU trap messages to be reported locally.

Select Use different ID for each alarm type if you want each type of alarm to receive a unique ID.

Select Send “clear” traps with zero severity if you want a trap with a “clear” severity (instead of the alarm's
original severity) to be sent to the IP addresses you specified.

5. For

CLLI (Common Language Location Identifier), enter up to 18 characters that will represent your system

ID when traps are sent.

6. For

Heartbeat Period, a heartbeat signal will be generated every x minutes (the number you enter) to tell your

system that the trap mechanism is working.

7. Click

Apply to save the settings.

External Alarms Setup

The procedure detailed in this section is required only if alarms generated by external equipment are connected to
the IDU, or if the IDU alarm outputs are connected to other equipment (using the alarms I/O connector).

The IDU has eight external alarm inputs and five external alarm outputs. Since each of the three levels support five
outputs, the system uses the OR function between the outputs of each floor, and accordingly generates the alarm.

1.

Select the middle floor of the IDU, and select Configuration, IDU, External Alarms.

Or, click the External Alarms icon

.

Or, click the EXT ALARM IN icon on the IDU front panel

.

The Input/Output External Alarms window appears.