2 what to do if something unusual occurs (gt30) – Motorola GT10 User Manual

Page 162

Advertising
background image

GT10/GT30

9.2

What to Do If Something Unusual Occurs (GT30)

139

9.2

What to Do If Something Unusual Occurs (GT30)

Problem

Cause

Solution

Related

Screen is

blank

1) Power is not on.
2) (When only lamp and message parts

are configured to the base screen)

Value of substitute reference device

value does not exist in substitute data.

1) Supply 24V DC power to unit.
2) Check the address of the substitute

reference device and the device val-

ues on the PLC side.

page 21
GTWIN HELP

Error code

[ER**]

appears at

the top right

of the screen

An error has occurred in communication

between the GT30 and an external de-

vice (e.g. PLC).

[Troubleshooting error codes] are listed

on page 142. Refer to this section for de-

tails.

page 142

Screen

displays

[No Screen

data]

There is no base screen data in the

GT30. (Appears even when GT30 con-

figuration data exists.)

Transfer base screen data from GTWIN.

GTWIN HELP

Screen

displays

[Screen No.

Error]

1) Screen settings from the PLC, the

GT30’s switch part or the auto–paging

indicate an unregistered screen num-

ber.

2) When bringing up the keyboard screen

during data input, an unregistered key-

board screen number was specified.

3) GT30 configuration data and keyboard

screen data exist in the GT30, but

there is no base screen data.

1) Create and register screen content or

specify the correct screen number.

2) Create and register keyboard screen

or specify the correct keyboard num-

ber.

3) Transfer base screen data from

GTWIN.

page 118

GTWIN HELP

GTWIN HELP

Screen

displays

[Memory is

Full]

The total capacity of transferred base

screen data exceeds capacity of the

GT30.

(Monochrome: 1.5 M bytes, color: 3.25 M

bytes)

Delete part of the base screen data so

that the total capacity doesn’t exceed the

capacity of GT30. Data capacity can be

checked by going to [View (V)] →

[Memory Usage Conditions] on GTWIN

menu bar.

GTWIN HELP

An

unspecified

screen

appeared /

there is

trouble when

switching

screens

1) The screen specification in the PLC

screen setting, the GT30 switch part

or the auto–paging is wrong.

2) The startup screen is specified in the

GT30 configuration settings (GTWIN).

3) An erroneous device or value is speci-

fied in the first word of the basic com-

munication area word device.

1) Specify the correct screen number.
2) Check the start–up screen setting for

the GT30 configuration settings in

GTWIN. Delete unnecessary settings

and re–transfer configuration data.

3) Check the device content specified on

the PLC side in the first word of the

basic communication area. (Do not

use the basic communication area

with ladder programs.)

page 118
page 115

page 37 to

page 38

Screen

doesn’t

switch

1) No screen number has been written to

the screen setting area (the first word

in the basic communication area word

device) from the PLC.

2) The screen number to which you are

attempting to switch has already been

written from the PLC to the screen set-

ting area (the first word in the basic

communication area word device).

1) Specify correct screen number.
2) Refer to page 119 [If the screen does

not change as expected]. (Do not use

the basic communication area with lad-

der programs.)

page 118
page 119

Advertising