3 error codes and how to handle them, 1 gt series error codes, Gt series error codes – Motorola GT10 User Manual

Page 165

Advertising
background image

GT10/GT30

9.3 Error Codes and How to Handle Them

142

9.3

Error Codes and How to Handle Them

When an error occurs in the GT series, an error code displays at the top right of the

screen. There are two types of error codes:

GT series error codes

PLC error codes

ER XX

Error code display

9.3.1

GT Series Error Codes

When connected to a FP series PLC
The following three types of error codes are displayed when there is an error in the GT

main unit:

Code no.

Content

Cause and solution

FF

Time up error

No response from the PLC.

1) The PLC connection cable is disconnected. Check the connection

cable to make sure it is connected.

2) There is a temporary error due to noise, etc. Re–supply power to the

PLC and GT main unit.

21

Data error

A data error occurred dur-

ing communication.

1) An error exists in the communication condition settings. Check the

PLC and GT main unit communication speed and transfer format.

2) There is a temporary error due to noise, etc. Re–supply power to the

PLC and GT main unit.

22

Overrun error

The GT main unit cannot

receive data.

The reception buffer in the GT main unit is overflowing.

There could be an error in the PLC.

Re–supply power to the PLC and GT main unit.

When connected to a PLC (FX) series made by Mitsubishi Electric
The following four types of error codes are displayed when there is an error in the GT

main unit:

Code no.

Content

Cause and solution

FF

Time up error

No response from the PLC.

Check the connection cable to make sure it is connected.

10

Data error

A data error occurred dur-

ing communication.

Check to see if there is an error in the communication parameters

settings.

12

Overrun error

The GT main unit cannot

receive data.

The problem may be caused by a runaway PLC.

61

PLC error

A NAK error has been re-

turned by the PLC.

Check the PLC settings.

Advertising