background image

GT10/GT30

4.10 Through Function

60

4.10 Through Function

With the GT series, communication can be set to take place automatically between the

COM. and TOOL ports in a “through function”. When the FP series tool software

installed in the computer connected to the GT series as shown below is booted, PLC

programs can be edited through the GT series.

The through function does not require any special settings, and is always in the standby

mode.

PLC

GT10/GT30

Connected by cable

to the COM. port or

TOOL port of the PLC

Screen

transfer

cable

AFC8513

Screen data

being sent

and received

Screen creation tool GTWIN

FP series programming tool

FPWIN Pro or FPWIN GR

Personal computer

FPWIN Pro or FPWIN GR are booted

on the computer being used to edit the

GT series screens, and the PLC pro-

grams can be edited and monitored via

the GT series.

PLC debugging

CAUTION

Precautions when using the through function

The system should be set up so that the interval for communication

retries in the FP series software (FPWIN Pro or FPWIN GR) (A) is

larger than that of the GT10 COM. port (B), meaning (A) > (B). If the

system is set up so that A = B or A < B, the through function will not

work properly.

Restrictions on COM. port connections

If the GT series is connected to the COM. port of the PLC, please be

aware that some functions cannot be used, such as rewriting in the

RUN mode in FPWIN Pro or FPWIN GR.

Precautions when connecting the FP Programmer II to the TOOL

port

If the FP Programmer II is connected to the TOOL port of the GT

series, the operating voltage of the GT series should be set to 25V

DC or less. Also, the GT series should not be left connected to the