GT10/GT30

4.8 Connecting the FP–M

56

4.8

Connecting the FP–M

4.8.1

Connecting to the COM. Port

AIP81842D

GT10

FP–M COM. port

GT30

FP–M communication format settings

System register no. Item

Value Set

System register value

412

Selection of target use of RS232C port

Computer link

K1

413

Data length

8 bits

K3

Parity check

Yes

Parity setting

Odd

Stop bits

1 bit

Line return code

CR

Start code

No STX

414

Baud rate setting

19200 bits/s

K0

415

Unit number

1

K1

416

Modem connection

No connection H0

PLC communication cable: D–sub 9–pin loose–wire cable (AIP81842D)

1

2

3

4

5

6

7

8

9

Signals on D–sub side

Pin no.

Wire color

GT COM port

1

––

––

2

White

RD

3

Green

SD

4

––

5

––

6

––

––

7

Brown

GND

8

––

––

9

––

––

Specifications

Length

Product no.

D–sub 9–pin

Single–side

loose wiring

AIP81842D

2m

5mm

35mm

2000mm

Wires’ cross section: 0.25mm

2