1 connecting the fp-sigma, 1 connecting to the com.port, 1 connecting the fp–sigma – Motorola GT10 User Manual

Page 65: Connecting to the com. port, 1 connecting to the com. port, Fp σ communication format settings, Connecting to the fp σ com. port

Advertising
background image

GT10/GT30

4.1 Connecting the FP–Sigma

42

4.1

Connecting the FP–Sigma

4.1.1

Connecting to the COM. Port

Loose–wire connection

FPΣ COM. port

GT10

GT30

RS232C

FPG–COM1

SG

CS

RS

RD

SD

AFPG801

MODE

1 2 3 4

ON

OFF

COM. (RS232C)

SD RD RS CS GND

TOOL (RS232C)

24V

FPΣ communication format settings

When using COM. Port 1

When using COM. Port

2

System

register no.

Item

Value Set

System

register no.

Item

Value Set

410

COM. Port 1

Unit number

1

411

COM. Port 2

Unit number

1

412

COM. Port 1

Communication

mode

Computer link

No modem

connection

412

COM. Port 2

Communication

mode

Computer link

No modem

connection

413

Data length

8 bits

414

Data length

8 bits

Parity check

Yes, Odd

Parity check

Yes, Odd

Stop bits

1 bit

Stop bits

1 bit

Line return code CR

Line return code CR

Start code

No STX

Start code

No STX

415

COM. Port 1

Communication

speed setting

19200 bits/s

415

COM. Port 2

Communication

speed setting

19200 bits/s

Connecting to the FPΣ COM. port

FPΣ

PLC side

SD

SD

RD

RD

RS

RS

CS

CS

GND

GND

When using the RS232C 1–channel type

Pin no.

Abbreviation

SD

SD

RD

RD

RS

RS

CS

CS

GND

GND

Pin no.

Abbreviation

S1

SD

R1

RD

S2

RS

R2

CS

GND

GND

Pin no.

Abbreviation

SD

SD

RD

RD

RS

RS

CS

CS

GND

GND

Pin no.

Abbreviation

When using the RS232C 1–channel type,

the section between the RS and CS signals

on the PLC side should be shorted.

GT main unit side

PLC side

When using the RS232C 2–channel type

GT main unit side

GT10/GT30

Advertising