GT10/GT30

4.7 Connecting the FP10SH/FP3 CCU

55

4.7

Connecting the FP10SH/FP3 CCU

AIP81842D

GT10

FP3 computer communication unit

GT30

DIP switch settings on reverse side of FP3 computer communication unit

SW No. Setting contents Value Set

Switch status

1

ON

2

Transfer speed

19200 bits/s

OFF

3

p

/

OFF

4

Data length

8 bits

ON

5

Parity check

Odd parity

ON

6

Parity check

Odd parity

OFF

7

Stop bit length

1 bit

OFF

8

Control signals

CS, RS invalid OFF

PLC communication cable: D–sub 9–pin loose–wire cable (AIP81842D)

1

2

3

4

5

6

7

8

9

Signals on D–sub side

Pin no.

Wire color

GT COM port

1

––

––

2

White

RD

3

Green

SD

4

––

5

––

6

––

––

7

Brown

GND

8

––

––

9

––

––

Specifications

Length

Product no.

D–sub 9–pin

Single–side

loose wiring

AIP81842D

2m

5mm

35mm

2000mm

Wires’ cross section: 0.25mm

2

Connecting to the FP3 computer communication unit (CCU)

1

FG

SD

RS

SG

CS

RD

2
3

4

5

6

N.C.

7

8

9

N.C.

ER

SD

SD

RD

CS

GND

RS

RD

RS

CS
GND

1

2

3

4

5

6

7

8

9

GT10/GT30

Pin no. on PLC side

No. 3 (green)

No. 2 (white)

No. 7 (brown)

PLC side

GT main unit side

Pin no.

Pin no. Abbreviation

Abbreviation