15.2.9 RS-232 Port

The unit is equipped with an RS-232 port for connecting a terminal or PC.
See Figure 29 for the port’s location.
See 12.1 - Using the RS-232 Port for instructions on using a PC terminal with the unit.

15.2.10Terminal Port Connections

The system has an asynchronous serial port configured as Data Terminal Equipment for terminal

access only (half duplex). The CPU services the terminal port with no handshaking. The serial port

conforms to RS-232 levels with a data format of 9600 Baud, 1 start bit, 8 data bits, and no parity bits.

The serial port is 1000 Volt DC isolated (non-SELV) and ESD protected to 15kV air discharge. The

connector is a 6 Pin MTA plug with connections shown below.

A DB9 male connector is added and connected parallel to the 6 position header. It is configured as

DTE.

Table 22

MTA Plug Pinout

Pin

Signal Name

Function / Comments

1

ISO_GND

Isolated service terminal ground

2

ISO_TXD

Isolated service terminal transmit output

3

ISO_RXD

Isolated service terminal receive input

4 NC

No

Connection

5 NC

No

Connection

6 NC

No

Connection

Table 23

DB9 Pinout

Pin

Signal Name

Function / Comments

1 NC

No

Connection

2

ISO_RXD

Isolated service terminal transmit output

3

ISO_TXD

Isolated service terminal receive input

4 NC

No

Connection

5

ISO_GND

Isolated service terminal ground

6 NC

No

Connection

7 NC

No

Connection

8 NC

No

Connection

9 NC

No

Connection