Installation Drawings

38

Figure 26 Control wiring for comms board (see Figure 27 on page 39 for internal modem wiring)

PS213003 Rev. 2

COMMS BOARD 02-810015-XX

TB51

TB55

TB56

J81

EXTERNAL MODEM

SEE DETAIL A

SITESCAN

SEE DETAIL B

NO CUSTOMER CONNECTION

NO CUSTOMER CONNECTION

DETAIL B

TB55

SEE NOTES 1 & 2

CUSTOMER SUPPLIED

INTERCONNECTING CABLE TO SITESCAN

3

2

1

-

BOARD.

AND LOCAL ELECTRICAL CODES.

6. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL

OF STATIC TRANSFER SWITCH FOR LOCATION OF COMMS

5. REFER TO CONTROL CONNECTION LOCATION DIAGRAM

SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS

4. ALL CONTROL WIRING (BY OTHERS) MUST BE RUN

SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

MANUAL FOR CONFIGURING THE COMMS BOARD.

3. REFER TO INSTALLATION, OPERATION & MAINTENANCE

2. SIGNAL VOLTAGE 5VDC, CURRENT 10mA.

NOTES:

+

J81

DETAIL A

1

23

4

56

7

89

D CD

RX

TX

DTR

G N

D

D SR

RTS

CTS

RI

CUSTOMER SUPPLIED

INTERCONNECTING CABLE

TO EXTERNAL MODEM

SEE NOTE 2

WITH TWISTED PAIR CABLE #22 AWG 300V MINIMUM.

1. MAXIMUM CABLE LENGTH 1000 FEET (300 METERS)