3 system grounding, 4 control wiring connections, System grounding – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 19: Control wiring connections, Figure 4, Warning

Advertising
background image

Power and Control Wiring

11

5.3

System Grounding

Equipment grounding — Grounding is primarily for equipment and personnel safety, although

proper grounding also enhances equipment performance.
All input and output power feeds must include an equipment grounding means as required by the

NEC and local codes.
An insulated equipment ground conductor is recommended to run with each input and output power

feed. The equipment ground conductors should be at least the minimum size conductor per the NEC

based on the upstream overcurrent protection device.

4-Wire-Plus-Ground Systems — When 4-wire-plus-ground input feeds are utilized, the input power

sources must be properly grounded. Because the neutral is not switched by the STS2, the neutrals of

the two power sources are solidly interconnected. The NEC prohibits grounding a power source at

more than one point. Connecting the neutrals of two grounded power sources together effectively

grounds each of the sources at more than one point, which allows neutral current to flow on the

ground system, defeats ground fault protection, creates a safety hazard, and violates the NEC.
Where possible, the two power sources should be located in close proximity and a single

neutral-to-ground bond made (as shown in Figure 4 on page 11 or as is typical with a double-

ended substation).

Figure 4

Typical one-line diagram of two PDUs and a static transfer switch

5.4

Control Wiring Connections

No control wiring is needed on the standard STS2. Only certain options require external control wir-

ing. See 6.0 - Options on page 13 for details

!

WARNING

If conduit is used as a grounding means, adequate electrical continuity must be maintained at

all conduit connections. The use of isolating bushings with a metal conduit can be a safety

hazard and is not recommended.

CB5

STS1

STS2

CB1

CB2

CB3

CB4

K1

K2

K3

K2

K3

K1

225A

225A

225A

225A

225A

225A

ISOLATION
TRANSFORMER

SOURCE 2

MICB2

SOURCE 1

ISOLATION
TRANSFORMER

MICB1

SS1

SS2

Advertising