Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 83

Advertising
background image

Alarm and Faults

75

024

CB2 SHUNT TRIP FAIL

CB2 shunt trip failed.

D, A, E

064

HEATSINK OVERTEMP

Heatsink has exceeded the recommended temperature.

A, E

067

S1 UV

Source 1 under voltage, fast detection.

A, E

068

S1 UV (RMS)

Source 1 under voltage, slow detection.

L, A, E

069

S1 OV

Source 1 over voltage

A, E

070

S1 OF/UF

Source 1 over frequency/under frequency

A, E

071

S1 FAIL

Source 1 failure.

A, E

072

S2 UV

Source 2 under voltage, fast detection.

A, E

073

S2 UV (RMS)

Source 2 under voltage, slow detection.

A, E

074

S2 OV

Source 2 over voltage.

A, E

075

S2 OF/UF

Source 2 over frequency/under frequency.

A, E

076

S2 FAIL

Source 2 failure.

A, E

077

S1 OVERCURRENT

Source 1 over current.

A, E

078

S2 OVERCURRENT

Source 2 over current.

A, E

079

S1 I-PEAK

I-PK on Source 1.

A, F, E

080

S2 I-PEAK

I-PK on Source 2.

A, F, E

081

SOURCES OUT OF SYNC

Source 1 and Source 2 are out of synchronization.

A, E

082

LOAD ON ALT SOURCE

The output load is running on the alternate source.

A, E

083

AUTO REXFER INHIBIT

Automatic retransfer is inhibited.

A, E

084

CB1 (S1) OPEN

Source 1, Circuit Breaker 1 is open.

A, E

085

CB2 (S2) OPEN

Source 2, Circuit Breaker 2 is open.

A, E

086

CB4 (S1 BYP) CLOSED

Source 1 on bypass, Circuit Breaker 4 is closed.

A, E

087

CB5 (S2 BYP) CLOSED

Source 2 on bypass, Circuit Breaker 5 is closed.

A, E

088

CB3 (OUTPUT) OPEN

Output circuit breaker (CB3) is open.

A, E

089

CB3A (OUTPUT) OPEN

Output circuit breaker (CB3A) is open.

A, E

090

S1 PHASE ROT ERROR

Source 1 phase rotation error.

A, E

091

S2 PHASE ROT ERROR

Source 2 phase rotation error.

A, E

092

TRANSFER INHIBITED

Transfer inhibited.

A, E

093

OUTPUT UV

Output is under voltage.

D, F, A, E

120

121

122

123

124

125

126

127

INPUT CONTACT #1

INPUT CONTACT #2

INPUT CONTACT #3

INPUT CONTACT #4

INPUT CONTACT #5

INPUT CONTACT #6

INPUT CONTACT #7

INPUT CONTACT #8

Input Contact # x is an optional alarm input. The alarm name

can be programmed with an alarm name from the Input

Contactor Isolator settings option under the Comm Options.

See Configuring the Input Contact Isolator Settings on

page 95. The alarm is sent to Monitor DSP. The LCD logs

the alarm with the programmed name. Monitor DSP logs it

with the generic name which is how it is reported to the SVT

query.

A, E

128

CONFIG MODIFIED

A set point configuration has changed.

A, E

129

PASSWORD CHANGED

The password for touch screen access has been modified

and saved.

A, E

130

TIME REPROGRAMMED

The system’s time has been reset and saved.

A, E

131

DATE REPROGRAMMED

The system’s date has been reset and saved.

A, E

132

EVENT LOG CLEARED

The event log has been erased.

A, E

133

HIST LOGS CLEARED

Both History Logs have been erased.

A, E

134

HIST LOGS FULL

Both History Logs have been written and no more history logs

can be written without clearing one of the logs.

A, E

Table 9

Event Messages

ID

Alarm Message

Description/Cause

Action