Figure 20 circuit breaker schedule – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 40

Advertising
background image

Installation Drawings

32

Figure 20 Circuit breaker schedule

CIRCUIT BREAKER SCHEDULE

100AMP TO 1000AMP

STATIC TRANSFER SWITCH 2

NOTES:

1. THE STS2 AUTOMATIC MOLDED CASE BREAKERS ARE 3 POLE, 600VAC RATED WITH MAGNETIC TRIP ONLY.

2. UPSTREAM DEVICES (BY OTHERS) MUST BE USED TO PROVIDE OVERCURRENT PROTECTION. UPSTREAM OVERCURRENT PROTECTION SHOULD HAVE AMPACITY EQUAL TO OR LESS THAN THE AMPERE RATING OF THE STATIC SWITCH MOLDED CASE BREAKER.

VOLTAGE

STATIC TRANSFER SWITCH 2, MOLDED CASE BREAKER SCHEDUL

E

1000A

400A

100A

250A

600A

800A

STS2

RATING

AMPACITY

VENDOR

TY

P

E

NSF

150A

SQD

WITHSTAND CURRENT

SQD

MERLIN GERIN

100K 65K 25K

NSF

NSJ

NSJ

PJ

PJ

250A

400A

600A

800A

1200A

100K 65K 25K

100K 100K 25K

100K 100K 25K

100K 65K 25K

100K 65K 25K

MERLIN GERIN

MERLIN GERIN

MERLIN GERIN

200-240V 380-480V

600V

200-240V 380-480V

600V

200-240V 380-480V

600V

200-240V 380-480V

600V

200-240V 380-480V

600V

200-240V 380-480V

600V