Figure 54 user settings dialog box, Source set points – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 98

Advertising
background image

STS2 Touch Screen Display

90

Figure 54 User settings dialog box

Source Set Points

The Source 1/2 Set Points allows you to configure trigger points for each input source (1 or 2) for the

STS2 via a keypad dialog or HI/LO dialog box. The source numbers do not designate the source as the

preferred or alternate source. The numbers simply identify the input source. See 10.2 - Manual

Transfer / Preferred Source Selection to set the preferred source.
The Set Points are based on values in relation to the nominal voltage required for the STS2. UV refers

to under voltage, meaning the amount of voltage below the nominal voltage. OV refers to over voltage,

or the amount of voltage over the nominal voltage.

Fast UV Setting (%)if the voltage drops below this set percentage of the nominal voltage, the

STS2 transfers from the current source to the opposite source.

Slow UV Setting (%)if the voltage remains this set percentage below the nominal voltage for

the period of the slow detection delay, the STS2 transfers from the current source to the opposite

source.

Slow UV detection delaythe number of cycles that the source must remain below the Slow UV

Setting before the STS2 transfers.

OV Setting (%)if the voltage exceeds this set percentage of the nominal voltage for the period of

the OV detection delay, the STS2 transfers from the current source to the opposite source.

OV Detection Delaythe number of cycles that the source must remain above the OV Setting

before the STS2 transfers sources.

I-PK Xfer Lockoutif current from the source exceeds this threshold, the STS2 disables source

transfers, and has to be reset either manually or automatically. The type of reset is configured

under the User Settings.

Advertising