0 power and control wiring, 1 input and output power connections, Ower – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 17: Ontrol, Iring, Input and output power connections, Figure 3, Typical static transfer switch one-line diagram, Warning, Caution

Advertising
background image

Power and Control Wiring

9

5.0

P

OWER

AND

C

ONTROL

W

IRING

All power and control wiring should be installed by a qualified electrician. All power and control wir-

ing must comply with the NEC and applicable local codes. Unless otherwise labeled, use the recom-

mended tightening torque as shown in Table 25 - Torque tightening.
The busbars are accessible through the front of the STS2 and designed to allow one-handed tightening.
Cables can be installed through the top or bottom of the unit through removable conduits plates.
See Figures 5 through 10 for wiring entrance locations.
Input wiring also can be installed under a raised floor to optional input junction boxes and cables,

when used.

5.1

Input And Output Power Connections

If the unit is furnished with input junction boxes, the input power connections are made to the input

power terminals located in the junction boxes. Input power cables, furnished with the input junction

boxes, are shipped unattached to the unit for connection between the junction boxes and the bus bars

provided inside the unit. Input junction box installation is discussed in 5.2 - Input Junction Box

Installation (Optional) on page 10.
If input junction boxes are not furnished, the input power connections are made to the bus bars pro-

vided inside the unit. These bus bars are accessible through the front of the unit.
Output power connections also are made to the bus bars provided inside the unit. These bus bars are

accessible through the front of the unit. See Figures 14 to 19 for details on the bus bars.

The two input power feeds (sources) to the STS2 should be from two independent sources to avoid a

common source failure.
To ensure proper operation of the STS2, the two input sources must be the same nominal voltage level

and phase rotation.
For uninterrupted automatic transfer, the two input sources should be synchronized within 15 degrees.

The STS2 is designed for operation with 3 or 4-wire solidly grounded sources only.
For 4-wire operation, the common source neutral must be connected to the STS2. See Figure 3 on

page 9 for a typical one-line diagram. Refer to Figures 14 to 19 for electrical field connections on all

units, with both single and dual output breakers.

Figure 3

Typical static transfer switch one-line diagram

!

WARNING

Risk of electric shock
Verify that all input power and control circuits are de-energized and locked out before making

connections inside unit.

!

CAUTION

Risk of unit damage.
The input sources to the static switch must be grounded-wye sources. Input sources other

than solidly grounded-wye sources may cause damage to the switch.

SOURCE 1

SOURCE 2

STS1

STS2

CB1

CB2

CB3

CB5

CB4

OUTPUT

K1

K2

K3

K2

K3

K1

SS1

SS2

Advertising