0 maintenance, 1 proper tightening of nuts and bolts, Table 25 torque tightening – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 145: 2 testing the sts2, 3 changing the air filter, Aintenance, Proper tightening of nuts and bolts, Testing the sts2, Changing the air filter, Table 25

Advertising
background image

Maintenance

137

17.0 M

AINTENANCE

Minimal periodic maintenance of the STS2 is required. As with all electrical distribution components,

the system should be regularly inspected for electrical connection integrity, signs of excessive temper-

atures, dirt accumulation, and proper system operation.

17.1 Proper Tightening of Nuts and Bolts

The recommended tightening torque for all nuts and bolts is as shown below, unless otherwise

labeled. All power connections are designed to remain at proper torque throughout the lifetime of the

unit.

17.2 Testing the STS2

The STS2 includes comprehensive system alarms and fault detection to identify operational prob-

lems. To increase the degree of confidence of proper system operation, periodic transfer tests can be

easily performed. For instructions for changing the preferred source and switching sources:

• For a Color Graphical Display unit, see 10.2 - Manual Transfer / Preferred Source

Selection on page 66.

• For an LED-equipped unit, see 14.2.2 - Manual Transfer / Preferred Source Selection on

page 106.

17.3 Changing the Air Filter

A standard furnace filter is installed behind the air intake in the front door. The air intake allows air

to circulate to cool the unit. Replace the filter when it becomes dirty and impedes air flow. The fre-

quency of changing or cleaning the filter depends on the location in which the unit is located.
The size of the filter is 1 in. x 25 in. x 25 in. (2.54 cm x 63.5 cm x 63.5 cm).

!

WARNING

Only qualified service personnel should perform maintenance on the static switch.
Lethal voltages exist inside the unit during normal operation.
The unit is supplied by multiple ac power sources. disconnect and lock-out all power sources

before working inside unit.

Table 25

Torque tightening

Bolt Shaft Size

Grade 5 -Imperial

Grade 8.8 -metric

Electrical Connections with

Belleville Washers

in-lb

(pound-inch)

N-m

(Newton-meter)

in-lb

(pound.inch)

N-m

(Newton.meter)

10-32

25

3

35

4

1/4-20

53

6

80

9.0

5/16-18

107

12

180

20.4

3/8-16

192

22

240

27.1

1/2-13

428

48

480

54.3

Advertising