Location Considerations

7

3.4

Altitude

The standard units are designed for full load operation up to 4000 feet (1200 m) above sea level. See

Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200 m).

Figure 1

Recommended derating for high altitude operation

Operation at full load at a higher altitude can be accommodated in ambient temperatures less than

104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load

operation at altitudes above 4000 feet (1200 m).

Figure 2

Maximum ambient temperature for full load operation at higher altitudes

Table 2

Altitude conversion—feet to meters

Feet

Meters

Feet

Meters

Altitude

4000

1200

Altitude

7500

2286

4500

1372

8000

2438

5000

1524

8500

2591

5500

1676

9000

2743

6000

1829

9500

2896

6500

1981

10000

3048

7000

2134

86

88

90

92

94

96

98

100

0

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

Altitude (Feet Above Sea Level)

Rating (%)

Max. Amb

ient T

emperatu

re

104.0 (40)

102.2 (39)

100.4 (38)

98.6 (37)

96.8 (36)

95.0 (35)

93.2 (34)

94.1 (33)

89.6 (32)

87.8 (31)

86.0 (30)

0

40

00

45

00

50

00

55

00

60

00

65

00

70

00

75

00

80

00

85

00

90

00

95

00

100

00

Altitude—Feet

°F (°C)

Advertising