Figure 30 outline drawing for input junction box, Figure 30 – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 50

Advertising
background image

Installation Drawings

42

Figure 30 Outline drawing for input junction box

PS211005 Rev. 1

32 [813]

F

16 3/4 [426]

16 [406]

16 [406]

A

100A

250A - 600A

RATING

17 1/2 [445]

DIMENSIONAL DATA - INCHES [mm]

BC

14 [356]

30 [762]

6 [152]

6 [152]

DE

12 [305]

10 [254]

33 [830]

INPUT JUNCTION BOX

(2) #6 AWG TO (2) 500 kcmil

GH

5/16 [8]

7/16 [11]

1 [25]

3 [76]

#6 AWG TO #2/0 AWG

WIRE SIZE RANGE

RECOMMENDED

LOCATION FOR

CUSTOMER CONNECTION

OF INPUT POWER

RACEWAY (BY OTHERS)

3 PHASE, 3 WIRE PLUS GROUND.

LOCATION OF FACTORY

SUPPLIED INPUT POWER

CABLE ASSEMBLY.

INPUT JUNCTION BOX

POWER TERMINAL BLOCK

A

B

C

G

G DIA.

HOLE

D

B

H

A

C

NOTES:

1. TWO JUNCTION BOXES ARE SUPPLIED, ONE FOR

EACH INPUT.

2. CABLE(S) ARE FACTORY SUPPLIED TO CONNECT THE JUNCTION BOX TO THE INPUT BUSBARS. SEE

ELECTRICAL FIELD CONNECTIONS DRAWING FOR

LOCATION.

3. PARALLEL CABLES ARE USED ON 400A AND 600A UNITS.