2 manual transfer / preferred source selection, Figure 47 source transfer screen, Manual transfer / preferred source selection – Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page 74

Advertising
background image

Operating Instructions for the Touch Screen Interface

66

10.2 Manual Transfer / Preferred Source Selection

The Source Transfer option (Source Xfers) in the touch screen menu allows you to select a preferred

source. Transfers are only permitted when the voltage and current are within their proper operating

range and the sources are synchronized. The Source Transfer screen indicates the synchronization

between the two sources, while the voltage and frequency are displayed on the Mimic. See Figure 47.

Transfer is inhibited if the deviation exceeds the parameter set in the Source Set Points. See User

Settings on page 89

If your system contains the LED front panel instead of the LCD touch screen, refer to 14.2.2 - Man-

ual Transfer / Preferred Source Selection for instructions on this procedure.

Figure 47 Source transfer screen

NOTE
If one source will be de-energized for an extended period (hours or days), set the unit to bypass

mode for the remaining source. Without using bypass, if a failure occurs in the switch

components for remaining source, the STS2 does not have a second source to switch to and the

load would not receive power. See Maintenance Bypass on page 67 for bypass instructions.