Installation Drawings

20

Figure 8

Outline drawing: 100 – 250amp STS2 with a key lockout switch option

GRAVITY

SIDE VIEW

TOP VIEW

BOTTOM ENTRY AREA

POWER CABLE

BOTTOM ENTRY AREA

CONTROL CABLE

BOTTOM VIEW

FRONT VIEW

EXHAUST

TOP ENTRY AREA

TOP ENTRY AREA

POWER CABLE

CONTROL CABLE

FRONT

FRONT

MAX. DOOR SWING 180°

CENTER

GRAVITY

CENTER

SEE DETAIL A

CENTERS

CASTER

CENTERS

12MM

AIR

CENTERS

CASTER

12MM CENTERS

AIR

FILTER

AIR INTAKE AREA

DO NOT

BLOCK

OUTLINE DRAWING

100 - 250 AMP WITH KEY LOCKOUT SWITCH OPTION

STATIC TRANSFER SWITCH 2

KEY

LOCKOUT

SWITCH

NOTES:

1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS). 2. 18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.

3. INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY. 4. HEAT OUTPUT: 2710 BTU/HR (0.80 KW/HR) MAX. FOR 100A SWITCH.

4680 BTU/HR (1.37 KW/HR)

MAX.

FOR

250A

SWITCH.

5. WEIGHT - 780 LBS. (354 KG)

6. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING. 7. KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.

8. COLOR - IBM OFF WHITE. 9. OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.

10. THREADED MOUNTING HOLES (SEE DETAIL A) ARE PROVIDED FOR SEISMIC ANCHORING OR FLOOR STAND. MOUNTING BOLTS MUST BE THREADED INTO THE UNIT MOUNTING HOLES FROM UNDERNEATH THE UNIT BASE. IF FLOOR STAND IS USED, THE CASTERS MUST REST ON THE FLOOR STAND TO

SUPPORT THE WEIGHT OF THE UNIT.

FRONT OF UNIT SHOWN

WITHOUT SIDE PANEL

DETAIL A

MOUNTING

HOLE (4) TYP

(SEE NOTES

10)

12MM DIA

THREADED

LEVELER

(620) 24.4

(238) 9.4

(343) 13.5

(326) 12.8

(130) 5.1

(756) 29.8

(736) 29.0

(548) 21.6

(272) 10.7

(488) 19.2

(815) 32.1

(1956) 77.0

(477) 18.8

(594) 23.4

(280) 11

.1

(213) 8.4

(1

16)

4.6

(932) 36.7

(762) 30

(619) 24.4

(265) 10.4

(376) 14.8

(546) 21.5

PS21

11

01 REV

. NO. 1